Phoenix PT 2X2-FF-ST-Surge protector-plug-in 2800755,PLUGTRAB, plug-in surge protection, for Foundation Fieldbus
| Product Type | Information Technology |
| product series | PLUGTRAB PT |
| IEC Category | C1 |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement level | C1 |
| C2 | |
| C3 | |
| D1 | |
| type | needle type |
| Bits | 5 |
| Surge protection fault alarm | None |
| line pairs per module | 2 |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 32V DC |
| Connection Mode | screw connection (connection to the base) |
| Dimensional drawing | |
| width | 17.7mm |
| height | 45mm |
| depth | 52mm |
| Horizontal stitch pitch | 1 Partition |
| full module width | 17.7mm |
| Full module height | 90mm |
| full module depth | 65.5mm |
| color | black (RAL 9005) |
| black (RAL 9005) | |
| flame retardant rating, according to UL 94 | V0 |
| Shell Material | PA |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC | 36V DC |
| Rated current | 1.6 A |
| UC, the effective working current IC | ≤ 5 µA |
| Residual Flow IPE | ≤ 5 & micro;A (with PT 4-BE) |
| Nominal discharge current In(8/20) & micro;s (core-core) | 100 A |
| Rated discharge current In(8/20)& micro;s (core-ground) | 10 kA |
| pulse discharge current Iimp(10/350) µs | 1 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-core) | 100 A |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) | 10 kA |
| rated power pulse current lan (1000)& micro;s (core-core) | 23 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak | ≤ 75V |
| Output voltage limit 1 kV/& micro;s (core-ground) peak | ≤ 1.3 kV (with PT 4-BE) |
| Output voltage limit 1 kV/& micro;s (core-core) static | ≤ 75V |
| voltage protection level Up(core-core) | ≤ 75V (C3 - 25 A) |
| voltage protection level Up(line-ground) | ≤ 1.3 kV (C1 - 1.5 kV) |
| ≤ 1.3 kV (C2 - 9 kV) | |
| ≤ 1.3 kV (D1 - 500 A) | |
| response time tA(core-core) | ≤ 1 ns |
| response time tA (core-ground) | ≤ 100 ns |
| the resistance of each path | ≤ 1 Ω |
| Surge protection fault alarm | None |
| Impact tolerance (line-line) | C3 - 25 A |
| Impact resistance (line-ground) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| D1 - 500 A |
| environmental conditions | |
| protection level | IP20 |
| ambient temperature (operation) | -40°C ... 85°C |
| ambient temperature (storage/transport) | -40°C ... 85°C |
| elevation | ≤ 2000 m (amsl) |