| movement direction |
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC |
6V DC |
| 4V AC |
| Rated current |
2 A (80 °C) |
| UC, the effective working current IC |
≤ 300 µA |
| Residual Flow IPE |
≤ 4 & micro;A (direct grounding) |
| ≤ 1 & micro;A (with PT 4 F-BE) |
| Nominal discharge current In(8/20) & micro;s (core-core) |
720 A |
| Rated discharge current In(8/20)& micro;s (core-ground) |
10 kA |
| pulse discharge current Iimp(10/350) µs |
2.5 kA (per path) |
| Total discharge current ITotal(8/20) µs |
20 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-core) |
720 A |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) |
10 kA |
| rated power pulse current lan (1000)& micro;s (core-core) |
160 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak |
≤ 13V |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 450V |
| ≤ 1 kV (with PT 4 F-BE) |
| Output voltage limit 1 kV/& micro;s (core-core) static |
≤ 10V |
| Residual voltage ln,(wire-wire) |
≤ 40V |
| Residual voltage lan(10/1000)& micro;s (wire-wire) |
≤ 20V |
| voltage protection level Up(core-core) |
≤ 30V (C1 - 1 kV / 500 A) |
| voltage protection level Up(line-ground) |
≤ 450V |
| ≤ 1 kV (with PT 4 F-BE) |
| response time tA(core-core) |
≤ 1 ns |
| response time tA (core-ground) |
≤ 100 ns |
| response time tA (line-signal ground) |
≤ 1 ns |
| input attenuation AE, symmetric. |
0.1 dB (≤ 250 kHz) |
| cut-off frequency fg(3 dB),50 Ω symmetric system |
Typical 1 MHz |
| Surge protection fault alarm |
None |
|
2 A (T) |
| Impact tolerance (line-line) |
C1 - 1 kV / 500 A |
| C3 - 100 A |
| Impact resistance (line-ground) |
C2 - 10 kV / 5 kA |
| D1 - 2.5 kA |