Phoenix CT 10-18FSR F/PE-24-Surge Protector-Plug-in 2807939,LSA-PLUS surge protection plug (COMTRAB CT 10), used for coarse/fine surge protection between 18 signal lines and GND And decoupling resistance and GND-PE coarse protection. Rated voltage: 24V DC. Model: 10 double lines.
| Product Type |
measurement and control technology |
| Product Series |
COMTRAB |
| IEC Category |
C1 |
| C2 |
| C3 |
| D1 |
| type |
LSA-PLUS module |
| Surge protection fault alarm |
None |
| can test protectors using the CHECKMASTER software tests: |
|
| Connection Mode |
can be inserted into COMTRAB-TERMIBLOCK and break/switch terminal strip LSA-PLUS |
| Dimensional drawing |
|
| width |
111mm |
| height |
22mm |
| depth |
68.5mm |
| color |
black (RAL 9005) |
| flame retardant rating, according to UL 94 |
V0 |
| Shell Material |
PBT |
| Mechanical parameters |
| Open Side Panel |
No |
| movement direction |
Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC |
40V DC |
| 28V AC |
| Rated current |
140 mA (25°C) |
| UC, the effective working current IC |
≤ 5 µA (18x) |
| Residual Flow IPE |
≤ 1 µA |
| Nominal discharge current In(8/20) & micro;s (core-core) |
5 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) |
5 kA |
| Total discharge current ITotal(8/20) µs |
10 kA |
| Maximum discharge current Imax(8/20)µs |
5 kA |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 60V (a, B) |
| Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 650V |
| Residual voltage ln,(wire-wire) |
≤ 85V (a-b) |
| In(line-signal ground) |
≤ 85V |
| response time tA(core-core) |
≤ 1 ns (a-b) |
| response time tA (core-ground) |
≤ 100 ns (a, B) |
| input attenuation AE, symmetrical. |
1.8 dB (1 MHz / 50 Ω) |
| 0.6 dB (400 kHz / 150 Ω) |
| 0.2 dB (60 kHz / 600 Ω) |
| cut-off frequency fg(3 dB),50 Ω symmetric system |
6 MHz (typical) |
| cut-off frequency fg(3 dB),150 Ω symmetric system |
2.5 MHz (typical) |
| cut-off frequency fg(3 dB),600 Ω symmetric system |
750 kHz (typical) |
| capacitance (core-ground) |
1.1 nF (1 MHz a... B) |
| the resistance of each path |
22 Ω ± 10% |
| Surge protection fault alarm |
None |
|
145 mA |
| Impact resistance (line-ground) |
D1 - 2.5 kA |
| Impact resistance (signal ground-ground) |
D1 - 2.5 kA |