protection channel |
L-N |
L-PE |
N-PE |
movement direction |
3L-N & N-PE |
Rated voltage UN |
240/415V AC (TN-S) |
240/415V AC (TT) |
Rated frequency fN |
50Hz (60 Hz) |
Maximum continuous operating voltage UC(L-N) |
335V AC |
Maximum continuous operating voltage UC(L-PE) |
335V AC |
Maximum continuous operating voltage UC(N-PE) |
264V AC |
Rated load current IL |
80 A |
Residual Flow IPE |
≤ 5 µA |
Standby power consumption PC |
≤ 810 mVA |
Nominal discharge current In(8/20) µs (L-N) |
12.5 kA |
Nominal discharge current In(8/20) µs (L-PE) |
12.5 kA |
Nominal discharge current In(8/20) µs (N-PE) |
50 kA |
Maximum discharge current Imax(8/20) µs |
50 kA |
impulse current (10/350) & micro;s (L-N), amount of charge |
6.25 |
impulse current (10/350) & micro;s (L-N), characteristic energy |
39 kJ/Ω |
impulse current (10/350) & micro;s (L-N), peak current Iimp |
12.5 kA |
impulse current (10/350) & micro;s (L-PE), amount of charge |
6.25 |
impulse current (10/350) & micro;s (L-PE), characteristic energy |
39 kJ/Ω |
impulse current (10/350) & micro;s (L-PE), peak current Iimp |
12.5 kA |
impulse current (10/350) & micro;s (N-PE), amount of charge |
25 |
impulse current (10/350) & micro;s (N-PE), characteristic energy |
625 kJ/Ω |
impulse current (10/350) & micro;s (N-PE), peak current Iimp |
50 kA |
Total discharge current Itotal(8/20) µs |
50 kA |
Total discharge current Itotal(10/350) µs |
50 kA |
Rated open freewheeling value Ifi(N-PE) |
100 A |
Rated short-circuit current ISCCR |
25 kA |
voltage protection level Up(L-N) |
≤ 1.2 kV |
≤ 1.6 kV (30 kA - 8/20 µs) |
voltage protection level Up(L-PE) |
≤ 2 kV |
voltage protection level Up(N-PE) |
≤ 1.7 kV |
Residual pressure Ures(L-N) |
≤ 1.2 kV (In) |
≤ 1.1 kV (10 kA) |
≤ 1 kV (at 5 kA) |
≤ 0.9 kV (at 3 kA) |
Residual pressure Ures(L-PE) |
≤ 2 kV (In) |
≤ 1.5 kV (10 kA) |
≤ 1.2 kV (at 5 kA) |
≤ 1.1 kV (at 3 kA) |
Residual pressure Ures(N-PE) |
≤ 0.6 kV (In) |
≤ 0.5 kV (10 kA) |
≤ 0.5 kV (at 5 kA) |
≤ 0.4 kV (at 3 kA) |
UT(L-N) |
415V AC (5 seconds/withstand mode) |
457V AC (120 min/safe failure mode) |