Phoenix CB E1 24DC/10A S-R P-electronic equipment circuit breaker 2800914, electronic equipment protection switch, 1 position, active current limit, output and reset input status, plug for the base.
Product Type | Equipment circuit breaker |
product series | CB E |
type | needle type |
Bits | 1 |
Channels | 1 |
insulation characteristics | |
pollution level | 2 |
Maximum load current | 8 A |
Single row maximum current | 8 A |
Overview | |
Nominal operating voltage | 24V DC |
18V DC ... 30V DC | |
Rated current IN | 10 A |
Rated isolation withstand voltage UI | 30V (load circuit) |
Rated overvoltage | 0.5 kV |
Breaking method | E (Electronic) |
required spare fuse | not required, built-in intrinsic safety components |
dielectric strength | 30V DC max (load circuit) |
Active Current Limit | type 1.25 x IN |
Fuse | electronic |
closed-circuit current I0 | Typical 8 mA (when switched on) |
Typical 11 mA (with status output) | |
power consumption | 1.46W (normal operation) |
temperature attenuation | 9 A (at 50°C) |
MTBF (IEC 61709, SN 29500) | 7200000 h (at 80% load at 25°C) |
6330000 h (at 40°C, 80% load) | |
voltage drop | 100 mV (IN) |
fail-safe components | 15 A DC |
Contact Type | without electrical isolation |
Load Circuit | |
Downtime | 100 ms (see time/current characteristic curve) |
undervoltage shutdown | < 14V (type off) |
> 17V (type on) | |
Maximum capacitive load | 20000 µF |
impact suppression | Typical 2 ms |
auxiliary contact | |
Contact Type | Positive switch signal output |
Reset | |
Input Voltage Range | 7V DC ... 30V DC (using falling edge reset) |
power consumption | Typical 2.6 mA (24V DC) |
pulse length | minimum 20 ms |
voltage | < 3V DC (low state) |
> 8V DC (high state) | |
Status Output | |
output voltage | 24V DC |
output current | maximum 0.2 A (short-circuit protection) |
Maximum load current | 8 A |
Connection Mode | pluggable |
width | 12.3mm |
height | 45mm |
depth | 52mm |
color | gray (RAL 7042) |
black (RAL 9005) | |
flame retardant rating, according to UL 94 | V-0 |