Phoenix AXL F AO8 1F-Analog Module 2688080,Axioline F, Analog Output Module, Analog Output: 8,0V ... 5V,-5V ... 5V,0V ... 10V,-10V ... 10V,0 mA ... 20 mA,4 mA ... 20 mA,-20 mA ... 20 mA, Connection Technology: 2-Wire System, Local Bus Transmission Rate: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
width
53.6mm
height
126.1mm
depth
54mm
Notes on dimensional data
using TH 35-7.5 rails (as EN60715).
Application Description
Application Description
for industrial applications only
Axioline F Local Bus
interfaces
2
Connection Mode
Bus Base Module
transmission speed
100 Mbps
Module
Input Address Area
16 Byte
Output Address Area
16 Byte
the required parameter data
27 Byte
7 Byte
simulation:
Output Name
analog output
Connection Mode
in-line connection
connection system
2 wire system
Notes on connection technology
Shielded, Twisted Pair
outputs
8
D/A conversion time
5 µs
D/A Converter Resolution
16 bits
protection circuit
short circuit and overload protection; electronic
Transient protection; Suppressor diode
data format
IB IL,S7 compatible
an expression for the output value
16-bit (15-bit sign)
Process Data Update
300 µs
current output signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
load/output load current output
to 500 Ω
voltage output signal
0V ... 5V
-5V ... 5V
0V ... 10V
-10V ... 10V
load/output load voltage output
> 2 kΩ
Allowable Cable Length
max. 250 m (reference cable type LiYCY (TP) n * 2*0.5 mm²)
Product Type
I/O components
product series
Axioline F
type
Modular structure
Installation position
any position (observe temperature attenuation)
Scope of supply
includes bus base module and Axioline F connector
insulation characteristics
Overvoltage Category
II (IEC 60664-1,EN 60664-1)
pollution level
2 (IEC 60664-1,EN 60664-1)
rated conditions
6.3W
potential: Axioline F local bus (UBus) power supply
supply voltage
5V DC (via bus base module)
current consumption
Maximum 130 mA (up to HW04)
Maximum 50 mA (from HW 05)
Typical 105 mA (up to HW04)
Typical 40 mA (from HW 05)
potential: analog module (UA) power supply
supply voltage
24V DC
Supply Voltage Range
19.2V DC ... 30V DC (includes all tolerances, including ripple)
current consumption
maximum 235 mA (8 current channels, 20 mA output)
Typical 110 mA (8 voltage channels, 10V output)
protection circuit
surge protection; electronic (35V, 0.5 s)
Polarity protection; up to HW 03: Polarity protection diodes from HW 04: Diodes in parallel, external with 5 A fuse (only for commissioning)