Phoenix AXL F AO8 1F-Analog Module 2688080,Axioline F, Analog Output Module, Analog Output: 8,0V ... 5V,-5V ... 5V,0V ... 10V,-10V ... 10V,0 mA ... 20 mA,4 mA ... 20 mA,-20 mA ... 20 mA, Connection Technology: 2-Wire System, Local Bus Transmission Rate: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

width 53.6mm
height 126.1mm
depth 54mm
Notes on dimensional data using TH 35-7.5 rails (as EN60715).

Application Description
Application Description for industrial applications only

Axioline F Local Bus
interfaces 2
Connection Mode Bus Base Module
transmission speed 100 Mbps

Module
Input Address Area 16 Byte
Output Address Area 16 Byte
the required parameter data 27 Byte
7 Byte

simulation:
Output Name analog output
Connection Mode in-line connection
connection system 2 wire system
Notes on connection technology Shielded, Twisted Pair
outputs 8
D/A conversion time 5 µs
D/A Converter Resolution 16 bits
protection circuit short circuit and overload protection; electronic
Transient protection; Suppressor diode
data format IB IL,S7 compatible
an expression for the output value 16-bit (15-bit sign)
Process Data Update 300 µs
current output signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
load/output load current output to 500 Ω
voltage output signal 0V ... 5V
-5V ... 5V
0V ... 10V
-10V ... 10V
load/output load voltage output > 2 kΩ
Allowable Cable Length max. 250 m (reference cable type LiYCY (TP) n * 2*0.5 mm²)

Product Type I/O components
product series Axioline F
type Modular structure
Installation position any position (observe temperature attenuation)
Scope of supply includes bus base module and Axioline F connector
insulation characteristics
Overvoltage Category II (IEC 60664-1,EN 60664-1)
pollution level 2 (IEC 60664-1,EN 60664-1)

rated conditions 6.3W
potential: Axioline F local bus (UBus) power supply
supply voltage 5V DC (via bus base module)
current consumption Maximum 130 mA (up to HW04)
Maximum 50 mA (from HW 05)
Typical 105 mA (up to HW04)
Typical 40 mA (from HW 05)
potential: analog module (UA) power supply
supply voltage 24V DC
Supply Voltage Range 19.2V DC ... 30V DC (includes all tolerances, including ripple)
current consumption maximum 235 mA (8 current channels, 20 mA output)
Typical 110 mA (8 voltage channels, 10V output)
protection circuit surge protection; electronic (35V, 0.5 s)
Polarity protection; up to HW 03: Polarity protection diodes from HW 04: Diodes in parallel, external with 5 A fuse (only for commissioning)
Transient protection; Suppressor diode
2688051

Phoenix AXL F AO8 1F-Analog Module 2688080

Product Center