Phoenix AXL F DI32/1 1F-digital quantity module 2688035,Axioline F, digital quantity input module, digital input: 32,24V DC, connection technology: 1-wire system, local bus transmission rate: 100 Mbps, protection level: IP20, including bus basic module and Axioline F connector

width 53.6mm
height 126.1mm
depth 54mm
Notes on dimensional data using TH 35-7.5 rails (as EN60715).

Application Description
Application Description for industrial applications only

Axioline F Local Bus
interfaces 2
Connection Mode Bus Base Module
transmission speed 100 Mbps

Module
Input Address Area 4 Byte
Output Address Area 0 Byte
the required parameter data 3 Byte
the required configuration data 6 Byte

digital quantity:
Enter Name Digital Input
Input Description EN 61131-2 types 1 and 3
Input Quantity 32
Connection Mode in-line connection
connection system 1 Wire
input voltage range, "0" signal -3V DC ... 5V DC
input voltage range, "1" signal 11V DC ... 30V DC
Rated input voltage UIN 24V DC
Rated input current UIN 2.4 mA
input filter time 3000 & micro;s (default (value))
1000 µs
< 100 &micro;s
protection circuit input polarity protection against reverse connection; shunt diode (30V,5 s)

Product Type I/O components
Product Series Axioline F
type Modular structure
Installation position any position (no temperature decay)
Scope of supply includes bus base module and Axioline F connector
insulation characteristics
Overvoltage Category II (IEC 60664-1,EN 60664-1)
pollution level 2 (IEC 60664-1,EN 60664-1)

rated conditions 3.65W
potential: Axioline F local bus (UBus) power supply
supply voltage 5V DC (via bus base module)
current consumption Maximum 120 mA (up to HW04)
Maximum 60 mA (from HW 05)
potential: feeding the digital input module (UI)
supply voltage 24V DC
Supply Voltage Range 19.2V DC ... 30V DC (includes all tolerances, including ripple)
current consumption max. 50 mA
protection circuit surge protection; electronic (35V, 0.5 s)
polarity protection; shunt diode with external 5 A fuse (for commissioning only)
electrical isolation/isolation for voltage range
test voltage: 5V local bus power supply (UBus)/24V supply (I/O) 500V AC, 50 Hz, 1 min
test voltage: 5V local bus power supply (UBus)/Functional Grounding 500V AC, 50 Hz, 1 min
test voltage: 24V supply (I/O)/function ground 500V AC, 50 Hz, 1 min