Phoenix QUINT-PS/3AC/24DC/20/CO-power supply, with protective coating 2320924, primary switching power supply QUINT POWER, screw connection, SFB Technology (Selective Fuse Breaking), input: 3 phases, output: 24V DC/20 A
| AC operation |
| Rated input voltage range |
3x 400V AC ... 500V AC |
| Input Voltage Range |
3x 320V AC ... 575V AC |
| 2x 360V AC ... 575V AC |
| 450V DC ... 800V DC |
| Supply Voltage |
AC/DC |
| Impulse current |
< 20 A (typical) |
| impulse current integral (I2t) |
< 3.2 A2s |
| AC frequency range |
45Hz ... 65Hz |
| DC Frequency Range |
0Hz |
| grid buffer time |
Typical 28 ms (400V AC) |
| Typical 43 ms (500V AC) |
| power consumption |
3x 1.6 A (400V AC) |
| 3x 1.3 A (500V AC) |
| 0.9 A (600V DC) |
| Rated power consumption |
783 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| Typical Response Time |
< 0.16 s |
| Allowable Spare Fuses |
B6 B10 B16 |
| Allowed DC Spare Fuses |
DC: Connect a suitable fuse |
| recommend use |
6 A ... 16 A (AC: characteristics B, C, D, K) |
| PE discharge current |
< 3.5 mA |
| efficiency |
> 93% (at 400V AC and rated) |
| Rated output voltage |
24V DC ±1% |
| output voltage (USet) setting range |
18V DC ... 29.5V DC (> 24V DC, stable capacity limit) |
| Rated output current (IN) |
20 A (-25°C ... 60 °C,UOUT= 24V DC) |
| POWER BOOST (IBoost) |
26 A (-25°C ... 40°C constant, UOUT= 24V DC) |
| selective fusing (ISFB) |
120 A (12 ms) |
| Type of thermal magnetic circuit breaker |
B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6 |
| Attenuation |
60°C ... 70°C (2.5 %/K) |
| feedback voltage resistance |
maximum 32V DC |
| output |
< 32V DC |
| control deviation |
<1% (load change, static 10%... 90%) |
| <3% (load change, dynamic 10%... 90%) |
| < 0.1 % (input voltage variation is ± 10 %) |
| residual wave |
< 40 mVSS(rated value) |
| output power |
480W |
| peak switching voltage rated load |
< 40 mVSS(rated, 20MHz) |
| maximum no-load power consumption |
11W |
| Maximum rated load power loss |
40W |
| rise time |
< 0.05 s (UOUT(10%... 90%)) |
| and connect |
Yes, for redundancy and increased capacity |
| Concatenation |
is |
| signal: DC OK active |
| Output Description |
UOUT>0.9xUN: High Signal |
| Switching voltage range |
18V ... 24V |
| output voltage |
+24V DC |
| Maximum starting current |
≤ 20 mA (short-circuit protection) |
| Continuous load current |
≤ 20 mA |
| signal: DC OK floating point |
| Output Description |
relay contacts, UOUT>0.9xUN: contact attraction |
| maximum switching voltage |
30V AC/DC |
| 24V DC |
| Maximum starting current |
0.5 A |
| 1 A |
| Continuous load current |
≤ 1 A |
| signal: POWER BOOST, active |
| Output Description |
IOUTN: High signal |
| Switching voltage range |
18V ... 24V |
| output voltage |
+24V DC |
| Maximum starting current |
≤ 20 mA (short-circuit protection) |
| Continuous load current |
≤ 20 mA |
| Input |
| Connection Mode |
screw connection |
| Minimum cross section of rigid conductor |
0.2 mm² |
| Maximum cross section of rigid conductor |
6 mm² |
| Minimum cross section of flexible lead |
0.2 mm² |
| Flexible lead maximum cross section |
4 mm² |
| Minimum Wire Cross Section AWG |
18 |
| Maximum conductor cross section AWG |
10 |
| stripping length |
7mm |
| thread |
M4 |
| Minimum tightening torque |
0.5 Nm |
| Maximum tightening torque |
0.6 Nm |