Phoenix QUINT-PS/1AC/12DC/20-power supply 2866721, primary switching power supply QUINT POWER, screw connection, SFB Technology (Selective Fuse Breaking), input: 1 phase, output: 12V DC/20 A
| AC operation |
| Rated input voltage range |
100V AC ... 240V AC |
| Input Voltage Range |
85V AC ... 264V AC |
| 90V DC ... 350V DC (UL 508: ≤ 250V DC) |
| AC input voltage range |
85V AC ... 264V AC |
| DC input voltage range |
90V DC ... 350V DC (UL 508: ≤ 250V DC) |
| maximum dielectric strength |
300V AC |
| Supply Voltage |
AC/DC |
| Impulse current |
< 20 A (typical) |
| impulse current integral (I2t) |
< 3.2 A2s |
| AC frequency range |
45Hz ... 65Hz |
| DC frequency range |
0Hz |
| grid buffer time |
Typical 40 ms (120V AC) |
| Typical 40 ms (230V AC) |
| power consumption |
2.4 A (120V AC) |
| 1.4 A (230V AC) |
| 2.5 A (110V DC) |
| 1.2 A (220V DC) |
| Rated power consumption |
311 VA |
| protection circuit |
transient surge protection; varistor |
| Typical Response Time |
< 1 s |
| input fuse |
12 A (slow fuse, internal) |
| Allowable Spare Fuses |
B10 B16 AC: |
| Allowed DC Spare Fuses |
DC: Connect a suitable fuse |
| recommend use |
10 A ... 16 A (AC: characteristics B, C, D, K) |
| PE discharge current |
< 3.5 mA |
| efficiency |
> 90% (230V AC and rated) |
| output characteristics |
U/ I |
| Rated output voltage |
12V DC ±1% |
| output voltage (USet) setting range |
5V DC ... 18V DC (> 12V DC, limited stable capacity) |
| Rated output current (IN) |
20 A (-25°C ... 60 °C) |
| POWER BOOST (IBoost) |
26 A (-25°C ... 40°C constant) |
| selective fusing (ISFB) |
120 A (12 ms) |
| Type of thermal magnetic circuit breaker |
B2 / B4 / B6 / B10 / C2 / C4 / C6 |
| Attenuation |
60°C ... 70°C (2.5 %/K) |
| feedback voltage resistance |
Max. 25V DC |
| output |
< 25V DC |
| control deviation |
<1% (load change, static 10%... 90%) |
| <2% (change of load, dynamic 10%... 90%) |
| < 0.1 % (input voltage variation is ± 10 %) |
| residual wave |
< 50 mVSS(rated value) |
| output power |
240W |
| maximum no-load power consumption |
6W |
| Maximum rated load power loss |
29W |
| rise time |
< 0.5 ms (UOUT(10%... 90%)) |
| and connect |
Yes, for redundancy and increased capacity |
| Concatenation |
is |
| signal: DC OK active |
| Output Description |
UOUT>0.9xUN: High Signal |
| Switching voltage range |
5V DC ... 12V DC |
| output voltage |
12V DC |
| Maximum starting current |
≤ 20 mA (short circuit protection) |
| Continuous load current |
≤ 20 mA |
| signal: DC OK floating point |
| Output Description |
relay contacts, UOUT>0.9xUN: contact attraction |
| maximum switching voltage |
30V AC |
| 24V DC |
| Maximum starting current |
0.5 A |
| 1 A |
| Continuous load current |
1 A |
| signal: POWER BOOST, active |
| Output Description |
IOUTN: High signal |
| Switching voltage range |
5V DC ... 12V DC |