Phoenix ELR H3-IES-SC- 24DC/500AC-2-hybrid motor starter 2900567, hybrid motor starter, used to start AC motors with more than 3 phases, up to 500V AC,2.4 A output current, 24V DC control voltage, Adjustable overload break and emergency stop function to SIL 3/PL e, screw connection.
| Product Type | hybrid motor starter |
| Product Series | CONTACTRON |
| Mode of operation | 100% operating factor |
| phase number | 3 |
| Motor Starter Type | direct starter |
| Switching frequency | ≤ 2Hz (depending on load) |
| rated conditions | 2.2W |
| Switching frequency | ≤ 2Hz (depending on load) |
| maximum power loss | 3.3W |
| minimum power loss | 1.1W |
| type of coordination | 1 |
| Power | |
| Rated control circuit supply voltage US | 24V DC |
| Control Supply Voltage Range | 19.2V DC ... 30V DC |
| Rated control supply current IS | 40 mA |
| protection circuit | surge protection |
| polarity protection | |
| insulation characteristics | |
| Rated insulation voltage | 500V |
| Rated overvoltage | 6 kV |
| Overvoltage Level | III |
| pollution level | 2 |
| control input and control supply voltage and insulation characteristics from auxiliary circuit to main circuit | safety insulation (IEC 60947-1) for operating voltages ≤ 300V AC |
| operating voltage 300V AC ... 500V AC (IEC 60947-1) | |
| control input and control supply voltage to auxiliary circuits | safety insulation (IEC 60947-1),≤ 300V AC in auxiliary circuits |
| control | |
| Enter Name | Control Input |
| Rated operating voltage UC | 24V DC |
| Trigger voltage range | 19.2V DC ... 30V DC |
| Rated operating current IC | 5 mA (input type 1) |
| Switch Threshold | 9.6V ("0" signal) |
| 19.2V ("1" signal) | |
| switch level | < 5V DC (for emergency stop) |
| Typical closing time | < 30 ms |
| protection circuit | polarity protection |
| AC output | |
| Rated operating voltage Ue | 500V AC |
| Operating voltage range | 42V AC ... 550V AC |
| Rated operating current Ie | 2.4 A (AC-51) |
| 2.4 A (AC-53a) | |
| mains frequency | 50/60Hz |
| Load current range | 180 mA ... 2.4 A (see decay curve) |
| action characteristics according to IEC 60947-4-2 | Class 10A |
| cooling time | 20 min (for automatic reset) |
| leakage current | 0 mA |
| protection circuit | surge protection |