Phoenix QUINT4-PS/1AC/24DC/20/-power supply 2904617, primary switched QUINT POWER power supply for DIN rail installation, optional output characteristic curve and SFB Technology (selective fusing technology), protective coating and built-in decoupling MOSFET, input: 1 phase, output: 24V DC/20 A
| Control Input (Configurable) Rem |
output power ON/OFF (SLEEP MODE) |
| Default (Value) |
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SNew) |
| AC operation |
| Network Type |
star network |
| Rated input voltage range |
100V AC ... 240V AC |
| Input Voltage Range |
100V AC ... 240V AC -15 % ... +10% |
| maximum dielectric strength |
300V AC 60 s |
| National Grid Typical Voltage |
120V AC |
| 230V AC |
| Supply Voltage |
AC |
| Impulse current |
Typical 10 A (at 25°C) |
| impulse current integral (I2t) |
< 0.3 A2s |
| Surge current limit |
10 A (after 1 ms) |
| AC frequency range |
50Hz ... 60Hz-10%... + 10% |
| frequency range (fN) |
50Hz ... 60Hz-10%... + 10% |
| 16.7Hz (in accordance with EN 50163) |
| grid buffer time |
Typical 36 ms (120V AC) |
| Typical 36 ms (230V AC) |
| power consumption |
6.8 A (100V AC) |
| 5.5 A (120V AC) |
| 2.8 A (230V AC) |
| 2.7 A (240V AC) |
| Rated power consumption |
520 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| Suction time |
< 1 s |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| input fuse |
12 A (slow fuse, internal) |
| recommend use |
10 A ... 16 A (characteristics B, C, D, K or similar) |
| PE discharge current |
< 3.5 mA |
| 1.7 mA (264V AC,60 Hz) |
| DC operation |
| input voltage |
Minimum 77V DC |
| Rated input voltage range |
110V DC ... 250V DC |
| Input Voltage Range |
110V DC ... 250V DC -18 % ... +40% |
| Supply Voltage |
DC |
| power consumption |
6 A (110V DC) |
| 2.5 A (250V DC) |
| efficiency |
Typical 92.7 % (120V AC) |
| Typical 94.2 % (230V AC) |
| Rated output voltage |
24V DC |
| output voltage (USet) setting range |
24V DC ... 28V DC (constant capacity) |
| Rated output current (IN) |
20 A |
| Static Boost (IStat.Boost) |
25 A |
| Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
| selective fusing (ISFB) |
120 A (15 ms) |
| Type of thermal magnetic circuit breaker |
A1...A16 / B2...B13 / C1...C6 / Z1...Z16 |
| Attenuation |
> 60°C ... 70°C (2.5 %/K) |
| feedback voltage resistance |
≤ 35V DC |
| output |
< 30V DC (double protection including shutdown within 20 ms) |