Phoenix QUINT4-PS/3AC/24DC/20/IOL-power supply 1151048, primary switching power supply QUINT POWER, screw connection, DIN rail installation, input: 3 phases, output: 24V DC/20 A

AC operation
Network Type star network
Rated input voltage range 3x 400V AC ... 500V AC
2x 400V AC ... 500V AC
Input Voltage Range 3x 400V AC ... 500V AC -20 % ... +10%
2x 400V AC ... 500V AC -10 % ... +10%
National Grid Typical Voltage 400V AC
480V AC
Supply Voltage AC/DC
Impulse current Typical 2 A (at 25°C)
impulse current integral (I2t) < 0.1 A2s
Surge current limit 2 A (after 1 ms)
AC frequency range 50Hz ... 60Hz-10%... + 10%
frequency range (fN) 50Hz ... 60Hz-10%... + 10%
grid buffer time Typical 33 ms (3x 400V AC)
Typical 33 ms (3x 480V AC)
power consumption 3x 0.99 A (400V AC)
3x 0.81 A (480V AC)
2x 1.62 A (400V AC)
2x 1.37 A (480V AC)
3x 0.8 A (500V AC)
2x 1.23 A (500V AC)
prevents polarity reversal is
Rated power consumption 541 VA
protection circuit transient surge protection; varistor, gas discharge tube
power factor (cos phi) 0.94
Suction time < 1 s
Typical Response Time 300 ms (from SLEEP MODE)
recommend use 3x 4 A ... 20 A (characteristic B, C or similar)
recommend ≥ 300V AC
PE discharge current < 3.5 mA
1.7 mA (550V AC, 60 Hz)
DC operation
Rated input voltage range ± 260V DC ... 300V DC
Input Voltage Range ± 260V DC ... 300V DC -13 % ... +30%
520V DC ... 600V DC -13 % ... +30 % (mid-point earthed)
power consumption 1.23 A (± 260V DC)
1.06 A (±300V DC)
recommend use 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
recommend ≥ 1000V DC

efficiency Typical 94.1 % (400V AC)
Typical 94.9 % (480V AC)
output characteristics U/ I Advanced
Rated output voltage 24V DC
output voltage (USet) setting range 24V DC ... 29.5V DC (constant capacity)
Rated output current (IN) 20 A
Static Boost (IStat.Boost) 25 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
2904602

Phoenix QUINT4-PS/3AC/24DC/20/IOL-Power 1151048