Phoenix QUINT4-PS/3AC/24DC/20/KONF1-power supply 1035480, QUINT POWE power supply for DIN rail installation, pre-configured model, primary switching mode, free selection of output characteristic curve and SFB (selective fusing) technology, input: 3 phases,
Output: 24V DC / 20 A
| Control Input (Configurable) Rem |
output power ON/OFF (SLEEP MODE) |
| Default (Value) |
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SGND) |
| AC operation |
| Network Type |
star network |
| Rated input voltage range |
3x 400V AC ... 500V AC |
| 2x 400V AC ... 500V AC |
| Input Voltage Range |
3x 400V AC ... 500V AC -20 % ... +10% |
| 2x 400V AC ... 500V AC -10 % ... +10% |
| National Grid Typical Voltage |
400V AC |
| 480V AC |
| Supply Voltage |
AC/DC |
| Impulse current |
Typical 2 A (at 25°C) |
| impulse current integral (I2t) |
< 0.1 A2s |
| Surge current limit |
3 A (after 1 ms) |
| AC frequency range |
50Hz ... 60Hz-10%... + 10% |
| frequency range (fN) |
50Hz ... 60Hz-10%... + 10% |
| grid buffer time |
≥ 25 ms (3x 400V AC) |
| ≥ 25 ms (3x 480V AC) |
| power consumption |
3x 0.99 A (400V AC) |
| 3x 0.81 A (480V AC) |
| 2x 1.62 A (400V AC) |
| 2x 1.37 A (480V AC) |
| 3x 0.8 A (500V AC) |
| 2x 1.23 A (500V AC) |
| Rated power consumption |
541 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| Suction time |
< 1 s |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| recommend use |
3x 4 A ... 20 A (characteristic B, C or similar) |
| recommend |
≥ 300V AC |
| PE discharge current |
< 3.5 mA |
| 1.7 mA (550V AC, 60 Hz) |
| DC operation |
| Rated input voltage range |
± 260V DC ... 300V DC |
| Input Voltage Range |
± 260V DC ... 300V DC -13 % ... +30% |
| Supply Voltage |
AC/DC |
| power consumption |
1.23 A (± 260V DC) |
| 1.06 A (±300V DC) |
| recommend use |
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) |
| recommend |
≥ 1000V DC |
| efficiency |
Typical 93.9 % (400V AC) |
| Typical 93.8 % (480V AC) |
| Rated output voltage |
26V DC |