Phoenix QUINT4-PS/3AC/24DC/40/VASS-power supply 1168603,QUINT POWER power supply, pre-configured and read-only model, primary switch mode, with set output voltage and adjustable signal, input: 3 phases, output: 24V DC/40 A

Control Input (Configurable) Rem output power ON/OFF (SLEEP MODE)
Default (Value) Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SNew)
AC operation
Network Type star network
Rated input voltage range 3x 400V AC ... 500V AC
2x 400V AC ... 500V AC
Input Voltage Range 3x 400V AC ... 500V AC -20 % ... +10%
2x 400V AC ... 500V AC -10 % ... +10%
National Grid Typical Voltage 400V AC
480V AC
Supply Voltage AC
Impulse current Typical 1.5 A (at 25°C)
impulse current integral (I2t) < 0.06 A2s
Surge current limit 0 A (after 1 ms)
frequency range (fN) 50Hz ... 60Hz-10%... + 10%
grid buffer time Typical 28 ms (3x 400V AC)
Typical 28 ms (3x 480V AC)
power consumption 3x 1.8 A (400V AC)
3x 1.5 A (480V AC)
2x 3 A (400V AC)
2x 2.5 A (480V AC)
3x 1.5 A (500V AC)
2x 2.4 A (500V AC)
Rated power consumption 1217 VA
protection circuit transient surge protection; varistor, gas discharge tube
power factor (cos phi) 0.91
Suction time < 1 s
Typical Response Time 300 ms (from SLEEP MODE)
recommend use 3x 4 A ... 20 A (characteristics B, C, D, K or similar)
recommend ≥ 300V AC
PE discharge current < 3.5 mA
1 mA (550V AC, 60 Hz)
DC operation
Rated input voltage range ± 260V DC ... 300V DC
Input Voltage Range ± 260V DC ... 300V DC -13 % ... +30%
Supply Voltage DC
power consumption 2.2 A (±260V DC)
1.9 A (±300V DC)
Rated power consumption 1217 VA
recommend use 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
recommend ≥ 1000V DC

efficiency Typical 95.7 % (400V AC)
Typical 95.7 % (480V AC)
Rated output voltage 26V DC
output voltage (USet) setting range 24V DC ... 29.5V DC (constant capacity)
Rated output current (IN) 40 A
Static Boost (IStat.Boost) 45 A
Dynamic Boost (IDyn.Boost) 60 A (5 s)
selective fusing (ISFB) 215 A (15 ms)
Type of thermal magnetic circuit breaker A1...A40 / B2...B25 / C1...C13 / Z1...Z16
feedback voltage resistance ≤ 35V DC
output ≤ 32V DC
control deviation < 0.5 % (static load change 10% ... 90%)
<3% (dynamic load change 10% ... 90%,(10Hz))
< 0.25 % (input voltage variation is ± 10 %)
residual wave < 50 mVSS(rated value)
2904603

Phoenix QUINT4-PS/3AC/24DC/40/VASS-Power 1168603

Product Center

PRODUCT CENTER