Phoenix QUINT4-PS/3AC/24DC/5-power supply 2904620,QUINT POWER power supply, primary switching mode, freely selectable output characteristic curve, SFB (selective fusing) technology, and NFC interface, input: 3 phase, output: 24V DC/5 A
| Control Input (Configurable) Rem |
output power ON/OFF (SLEEP MODE) |
| Default (Value) |
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SNew) |
| AC operation |
| Network Type |
star network |
| Rated input voltage range |
3x 400V AC ... 500V AC |
| 2x 400V AC ... 500V AC |
| Input Voltage Range |
3x 400V AC ... 500V AC -20 % ... +10% |
| 2x 400V AC ... 500V AC -10 % ... +10% |
| National Grid Typical Voltage |
400V AC |
| 480V AC |
| Supply Voltage |
AC |
| Impulse current |
Typical 11 A (at 25°C) |
| impulse current integral (I2t) |
< 0.2 A2s |
| Surge current limit |
11 A (after 1 ms) |
| AC frequency range |
50Hz ... 60Hz-10%... + 10% |
| frequency range (fN) |
50Hz ... 60Hz-10%... + 10% |
| grid buffer time |
Typical 34 ms (3x 400V AC) |
| Typical 50 ms (3x 480V AC) |
| power consumption |
3x 0.53 A (400V AC) |
| 3x 0.44 A (480V AC) |
| 2x 0.9 A (400V AC) |
| 2x 0.66 A (480V AC) |
| 3x 0.45 A (500V AC) |
| 2x 0.8 A (500V AC) |
| Rated power consumption |
283 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| power factor (cos phi) |
0.48 |
| Suction time |
< 500 ms |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| input fuse |
2 A (slow fuse, internal) |
| recommend use |
3x 6 A (characteristic B, C or similar) |
| recommend |
≥ 300V AC |
| PE discharge current |
< 3.5 mA |
| 1 mA (550V AC, 60 Hz) |
| DC operation |
| Rated input voltage range |
± 300V DC |
| Input Voltage Range |
± 260V DC ... 300V DC -25 % ... +30% |
| 520V DC ... 600V DC -25 % ... +30 % (mid-point earthed) |
| Supply Voltage |
DC |
| Surge current limit |
≤ 11 A (after 1 ms) |
| frequency range (fN) |
0Hz (DC) |
| power consumption |
0.3 A (±300V DC) |
| recommend use |
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) |
| recommend |
≥ 1000V DC |
| efficiency |
Typical 89% (400V AC) |
| Typical 87.5 % (480V AC) |
| output characteristics |
U/ I Advanced |
| Smart HICCUP |
| FUSE MODE |
| Rated output voltage |
24V DC |
| output voltage (USet) setting range |
24V DC ... 29.5V DC (constant capacity) |
| Rated output current (IN) |
5 A |
| Static Boost (IStat.Boost) |
6.25 A |