Phoenix QUINT4-PS/3AC/48DC/20-power supply 2904627,QUINT POWER primary switching power supply, using freely selectable output characteristic curve, SFB (selective fusing) technology and NFC interface, input: 3 phases, output: 48V DC/20 A
| Control Input (Configurable) Rem |
output power ON/OFF (SLEEP MODE) |
| Default (Value) |
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SGND) |
| AC operation |
| Network Type |
star network |
| Rated input voltage range |
3x 400V AC ... 500V AC |
| 2x 400V AC ... 500V AC |
| Input Voltage Range |
3x 400V AC ... 500V AC -20 % ... +10% |
| 2x 400V AC ... 500V AC -10 % ... +10% |
| National Grid Typical Voltage |
400V AC |
| 480V AC |
| Supply Voltage |
AC/DC |
| Impulse current |
Typical 1.5 A (at 25°C) |
| impulse current integral (I2t) |
< 0.06 A2s |
| Surge current limit |
2 A (after 1 ms) |
| AC frequency range |
50Hz ... 60Hz-10%... + 10% |
| frequency range (fN) |
50Hz ... 60Hz-10%... + 10% |
| grid buffer time |
Typical 26 ms (3x 400V AC) |
| Typical 26 ms (3x 480V AC) |
| power consumption |
3x 1.8 A (400V AC) |
| 3x 1.5 A (480V AC) |
| 2x 3 A (400V AC) |
| 2x 2.5 A (480V AC) |
| 3x 1.5 A (500V AC) |
| 2x 2.4 A (500V AC) |
| Rated power consumption |
1217 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| power factor (cos phi) |
0.95 |
| Suction time |
< 1 s |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| recommend use |
3x 4 A ... 20 A (characteristics B, C, D, K or similar) |
| recommend |
≥ 300V AC |
| PE discharge current |
< 3.5 mA |
| 1 mA (550V AC, 60 Hz) |
| DC operation |
| Rated input voltage range |
± 260V DC ... 300V DC |
| Input Voltage Range |
± 260V DC ... 300V DC -13 % ... +30% |
| 520V DC ... 600V DC -13 % ... +30 % (mid-point earthed) |
| power consumption |
2.2 A (±260V DC) |
| 1.9 A (±300V DC) |
| Rated power consumption |
1217 VA |
| recommend use |
1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms) |
| recommend |
≥ 1000V DC |
| efficiency |
Typical 95.9 % (400V AC) |
| Typical 96.2 % (480V AC) |
| Rated output voltage |
48V DC |
| output voltage (USet) setting range |
48V DC ... 56V DC (constant capacity) |
| Rated output current (IN) |
20 A |
| Static Boost (IStat.Boost) |
22.5 A |
| Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
| selective fusing (ISFB) |
105 A (15 ms) |
| Type of thermal magnetic circuit breaker |
A1...A20 / B2...B10 / C1...C6 / Z1...Z16 |
| Attenuation |
> 60°C ... 70°C (2.5 %/K) |
| feedback voltage resistance |
≤ 60V DC |
| output |
≤ 60V DC |
| control deviation |
< 0.5 % (static load change 10% ... 90%) |
| <2% (dynamic load change 10% ... 90%,(10Hz)) |