Phoenix QUINT-HP-UPS/120AC/1.5KVA/PT-uninterruptible power supply 1136804,QUINT AC UPS, IQ Technology, wall-mounted, input: 120V AC, output: 120V AC / 1500 VA.
input voltage
100V AC -10 % / +20%
110V AC -10 % / +20%
120V AC -10 % / +15%
130V AC -15 % / +10%
the voltage type of the supply voltage
AC
frequency range (fN)
47.5Hz ... 52.5Hz
57Hz ... 63Hz
Bypass Fuse
30 A T 250V
Allowable Spare Fuses
32 A (Listed breaker)
power consumption
rated 19 A (100V AC)
Rated 17.3 A (110V AC)
Rated 15.9 A (120V AC)
Rated 14.6 A (130V AC)
Maximum 25.8 A (100V AC)
Maximum 23.4 A (110V AC)
Maximum 21.5 A (120V AC)
max. 21 A (130V AC)
Rated short-circuit current-carrying capacity Icw
6 kA
classification according to IEC 62040-3
VFI-SS-111
efficiency
> 94% (100% load, battery charged)
> 90% (100% load, battery charged)
apparent power
1500 VA
Active power
1350W
power factor (cos phi)
0.9
amplitude factor
2.8
switching time
0 ms
and connect
yes.
maximum 3
Concatenation
No
Overload capacity trunk operation
120 % ... 150% (20 s/5 s, then switch to bypass operation)
Overload capacity battery operation
120... 150% (20 s / 5 s then off)
Overload Capacity Bypass Mode
120... 150% (for a while/20 s, then switch off)
Rated short-circuit current-carrying capacity Icw
6 kA
mains power supply
output voltage
100V AC ±2%
110V AC ±2%
120V AC ±2%
130V AC ±2%
Output Voltage Shape
pure sine wave
output current
rated 15 A (100V AC)
Rated 13.6 A (110V AC)
Rated 12.5 A (120V AC)
Rated 11.5 A (130V AC)
maximum no-load power consumption
28W
Maximum rated load power loss
75W (100% load, battery charged)
Rated output frequency
50Hz
60Hz
± 0.5 % (output frequency tolerance)
Electronic current limit
> 2,5 x Output: Current nom. (> 200 ms)
battery operation
maximum no-load power consumption
25W
Maximum rated load power loss
140W (100% load, battery charged)