Phoenix AXL F RTD4 XC 1H-Temperature Module 1035430,Axioline F, Temperature Recording Module, Analog Input: 4 (for Thermal Resistance Temperature Detector), Connection Technology: 2, 3, 4 Wire (Shielding), Local Bus Transmission Rate: 100 Mbps, Extreme Environment Model, Protection Level: IP20, Including Bus Base Module and Axioline F Connector

width 35mm
height 126.1mm
depth 54mm
Notes on dimensional data using TH 35-7.5 rails (as EN60715).

Application Description
Application Description for industrial applications only

Axioline F Local Bus
interfaces 2
Connection Mode Bus Base Module
transmission speed 100 Mbps

Module
Input Address Area 8 Byte
Output Address Area 0 Byte
the required parameter data 12 Byte
6 Byte

simulation
Enter Name Analog Input
Input Description Input for Resistance Temperature Sensor
Input Quantity 4 (for RTD)
Connection Mode in-line connection
connection system 2, 3, 4 wire (shielded)
A/D Converter Resolution 24.
Available Sensor Types (RTDs) Pt, Ni, KTY, Cu sensors
data format IB IL,S7 compatible
measurement value expression 16 bits (15 bits + sign bit)
input filter time 40 ms
60 ms
100 ms
120 ms (settable)
current power supply rating 1 mA (Pt 100,Ni 100, RLin500 Ω; pulse current, the specification is valid at the sampling stage)
210 µA (Pt 1000,Ni 1000,RLin5000 Ω; pulse current, the specification is valid at the sampling stage)
difference non-linearity Typical 1 ppm / ± 0.0001 % (in all series)
integrated non-linearity Typical 30 ppm / ± 0.003 % (Pt 100)
typical 20 ppm / ± 0.002 % (RLin500 Ω)
typical 200 ppm / ± 0.02 % (RLin5000 Ω)
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
protection circuit Short circuit protection for input, overload protection
input
Sensor Power Supply
2688310

Phoenix AXL F RTD4 XC 1H-Temperature Module 1035430