Phoenix AXL F RTD8 1F-temperature module 2688077,Axioline F, temperature recording module, analog input: 8 (for thermal resistance temperature detectors), connection technology: 2, 3, 4 wires (shielded), local bus transmission rate: 100 Mbps, protection level: IP20, including bus base module and Axioline F connector

width 53.6mm
height 126.1mm
depth 54mm
Notes on dimensional data using TH 35-7.5 rails (as EN60715).

Application Description
Application Description for industrial applications only

Axioline F Local Bus
interfaces 2
Connection Mode bus base module
transmission speed 100 Mbps

Module
Input Address Area 16 Byte
Output Address Area 0 Byte
the required parameter data 20 Byte
6 Byte

simulation
Enter Name Analog Input
Input Description Input for Resistance Temperature Sensor
Input Quantity 8 (for RTD)
Connection Mode in-line connection
connection system 2, 3, 4 wire (shielded)
A/D Converter Resolution 24.
Available Sensor Types (RTDs) Pt, Ni, KTY, Cu Sensors
data format IB IL,S7 Compatible
Measurement Value Expression 16 bits (15 bits + sign bit)
input filter time 40 ms
60 ms
100 ms
120 ms (settable)
current power supply rating 1 mA (Pt 100,Ni 100, RLin500 Ω; pulse current, the specification is valid at the sampling stage)
210 µA (Pt 1000,Ni 1000,RLin5000 Ω; pulse current, the specification is valid at the sampling stage)
difference non-linearity Typical 1 ppm / ± 0.0001 % (in all series)
integrated non-linearity Typical 30 ppm / ± 0.003 % (Pt 100)
typical 20 ppm / ± 0.002 % (RLin500 Ω)
typical 200 ppm / ± 0.02 % (RLin5000 Ω)
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
protection circuit Short circuit protection for input, overload protection
input
Sensor Power Supply
2688051

Phoenix AXL F RTD8 1F-Temperature Module 2688077

Product Center