Phoenix TRIO-PS-2G/3AC/24DC/40-power supply 2903156, suitable for DIN rail installation TRIO power supply, primary switching mode, input: 3 phases, output: 24V DC/40 A, dynamic power margin, quick connection without tools Technology, suitable for solid wires and flexible wires equipped with sleeves
AC operation
Network Type
star network
Rated input voltage range
3x 400V AC ... 500V AC
Input Voltage Range
3x 400V AC ... 500V AC -20 % ... +15%
National Grid Typical Voltage
3x 400V AC
3x 480V AC
Supply Voltage
AC
impulse current integral (I2t)
≤ 1.1 A2s
Surge current limit
35 A (after 1 ms)
AC frequency range
50Hz ... 60Hz
frequency range (fN)
50Hz ... 60Hz ± 5Hz
grid buffer time
> 10 ms (400V AC)
> 20 ms (480V AC)
power consumption
3x 1.9 A (400V AC)
3x 1.7 A (500V AC)
Rated power consumption
1335.1 VA
protection circuit
transient surge protection; varistor
power factor (cos phi)
0.77
Typical Response Time
< 1 s
input fuse
6.3 A (built-in (equipment protection))
recommend use
10 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 3.5 mA
< 2.5 mA (550V AC, 60 Hz)
Power factor
> 0.7 (400V AC)
> 0.7 (480V AC)
efficiency
Typical 93% (400V AC)
Typical 93.3 % (480V AC)
output characteristics
U/ I with dynamic load reserve
Rated output voltage
24V DC ±1%
output voltage (USet) setting range
24V DC ... 28V DC (> 24V DC, stable capacity limit)