Phoenix TRIO-PS67/1AC/24DC/10/IPD-power supply 1111664, primary switching power supply TRIO POWER, IPD plug-in connector with in-line spring connection, wall-mounted installation, input: 1 phase, output: 24V DC/10 A

AC operation
Power System Configuration star network (TN,TT,IT (PE))
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC ±10%
turn-on voltage > 75V AC
Shutdown Voltage < 70V AC
maximum dielectric strength ≤ 300V AC 15 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC
Impulse current ≤ 25 A (typical)
impulse current integral (I2t) < 0.5 A2s
Surge current limit Typical 25 A (after 1 ms)
AC frequency range 50Hz ... 60Hz ± 10%
frequency range (fN) 50Hz ... 60Hz ± 10%
grid buffer time > 15 ms (120V AC)
> 15 ms (230V AC)
power consumption 2.8 A (100V AC)
1.2 A (240V AC)
Rated power consumption 285 VA
protection circuit transient surge protection; varistor
power factor (cos phi) > 0.93
Suction time < 1 s
input fuse 6.3 A (built-in (equipment protection))
recommend use 6 A ... 16 A (US/CAN: branch circuit protection 20 A) (characteristics B, C, D, K or similar)
PE discharge current < 3.5 mA
DC operation
Rated input voltage range 110V DC ... 250V DC
Input Voltage Range 110V DC ... 250V DC ±10%
turn-on voltage ≥ 95V DC
Shutdown Voltage < 95V DC
Supply Voltage DC
grid buffer time > 15 ms
power consumption 2.4 A (110V DC)
1.1 A (250V DC)
power factor (cos phi) > 93

efficiency Typical 91% (120V AC)
Typical 92% (230V AC)
Rated output voltage 24V DC ±1 % (SELV)
Rated output current (IN) 10 A
Dynamic Boost (IDyn.Boost) 15 A (5 s)
Attenuation > 60°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output ≤ 30V DC
control deviation <1% (load change, static 10%... 90%)
<3% (dynamic load change 10%... 90%, 10Hz)
< 0.1 % (input voltage variation is ± 10 %)
residual wave ≤ 10 mVSS
1111634

Phoenix TRIO-PS67/1AC/24DC/10/IPD-Power 1111664

Product Center

PRODUCT CENTER