Phoenix TRIO-PS67/1AC/24DC/10/M12-power 1111634, primary switching power supply TRIO POWER, M12 circular connector, wall-mounted, input: 1 phase, output: 24V DC/10 A
| AC operation | |
| Power System Configuration | star network (TN,TT,IT (PE)) |
| Rated input voltage range | 100V AC ... 240V AC |
| Input Voltage Range | 100V AC ... 240V AC ±10% |
| turn-on voltage | > 75V AC |
| Shutdown Voltage | < 70V AC |
| maximum dielectric strength | ≤ 300V AC 15 s |
| National Grid Typical Voltage | 120V AC |
| 230V AC | |
| Supply Voltage | AC |
| Impulse current | ≤ 25 A (typical) |
| impulse current integral (I2t) | < 0.5 A2s |
| Surge current limit | Typical 25 A (after 1 ms) |
| AC frequency range | 50Hz ... 60Hz ± 10% |
| frequency range (fN) | 50Hz ... 60Hz ± 10% |
| grid buffer time | > 15 ms (120V AC) |
| > 15 ms (230V AC) | |
| power consumption | 2.8 A (100V AC) |
| 1.2 A (240V AC) | |
| Rated power consumption | 285 VA |
| protection circuit | transient surge protection; varistor |
| power factor (cos phi) | > 0.93 |
| Suction time | < 1 s |
| input fuse | 6.3 A (built-in (equipment protection)) |
| recommend use | 6 A ... 16 A (US/CAN: branch circuit protection 20 A) (characteristics B, C, D, K or similar) |
| PE discharge current | < 3.5 mA |
| DC operation | |
| Rated input voltage range | 110V DC ... 250V DC |
| Input Voltage Range | 110V DC ... 250V DC ±10% |
| turn-on voltage | ≥ 95V DC |
| Shutdown Voltage | < 95V DC |
| Supply Voltage | DC |
| grid buffer time | > 15 ms |
| power consumption | 2.4 A (110V DC) |
| 1.1 A (250V DC) | |
| power factor (cos phi) | > 93 |