Phoenix TRIO-PS67/1AC/24DC/3.75/INC-power 1278302, primary switching power supply TRIO POWER, 7/8 & Prime; circular connector, wall-mounted, input: 1 phase, output: 24V DC/3.75 A
| AC operation |
| Power System Configuration |
star network (TN,TT,IT (PE)) |
| Rated input voltage range |
100V AC ... 277V AC |
| Input Voltage Range |
100V AC ... 277V AC -15 % ... +10% |
| 115V AC ... 277V AC ±10 % (UL) |
| Attenuation |
< 100V AC ... 85V AC (1 %/V) |
| turn-on voltage |
≥ 80V AC |
| Shutdown Voltage |
< 75V AC |
| National Grid Typical Voltage |
120V AC |
| 230V AC |
| Supply Voltage |
AC/DC |
| Impulse current |
≤ 35 A (typical, 277V AC) |
| 17 A (Typical, 120V AC) |
| impulse current integral (I2t) |
< 0.45 A2s |
| AC frequency range |
50Hz ... 60Hz ± 10% |
| frequency range (fN) |
50Hz ... 60Hz ± 10% |
| grid buffer time |
> 25 ms (120V AC) |
| > 25 ms (230V AC) |
| power consumption |
1 A (100V AC) |
| 0.4 A (277V AC) |
| protection circuit |
transient surge protection; varistor |
| power factor (cos phi) |
> 0.92 |
| Suction time |
< 0.2 s |
| input fuse |
4 A (built-in (equipment protection)) |
| recommend use |
6 A ... 16 A/Canada: Branch circuit protection 20 A (characteristics B, C, D, K or similar) |
| PE discharge current |
< 0.5 mA |
| DC operation |
| Rated input voltage range |
110V DC ... 250V DC |
| Input Voltage Range |
110V DC ... 250V DC -20 % ... +10% |
| 120V DC ... 250V DC ±10 % (UL) |
| Attenuation |
< 110V DC ... 88V DC (1 %/V) |
| turn-on voltage |
≥ 75V DC |
| Shutdown Voltage |
< 70V DC |
| Supply Voltage |
AC/DC |
| power consumption |
0.88 A (110V DC) |
| 0.38 A (250V DC) |
| efficiency |
Typical 93% (120V AC) |
| 94% typical (230V AC) |
| Rated output voltage |
24V DC ±2 % (SELV) |
| Rated output current (IN) |
3.75 A (NEC Class 2 Output) |
| Attenuation |
> 60°C ... 70°C (2.0 %/K) |
| feedback voltage resistance |
≤ 35V DC |
| output |
≤ 35V DC |
| control deviation |
<1% (load change, static 10%... 90%) |