Phoenix PSR-MC32-3NO-1NC-24-230UC-SP-safety relay 2700525, safety relay, used for emergency stop, safety door and grating, safety level up to SIL 3, Cat. 4, PL e, single channel or dual channel operation, automatic or manual, controlled start, 3 enable current paths, 1 signal current path, US = 24 ... 230V AC/DC, pluggable in-line terminal

Product Type safety relay
Product Series PSRmini
Application Emergency stop button
safety door
electromagnetic switch
answering machine
grating
control Single and Dual Channel
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical Response Time < 150 ms (auto start)
< 100 ms (manual, monitoring start)
Typical startup time (Us) < 200 ms (when controlled via A1)
response time < 200 ms (when requested via A1; application deactivation via A1/A2 not allowed)
Typical release time < 20 ms (via sensor loop as required)
restart time < 1 s (start-up time)
Recovery Time < 500 ms (meets the requirements of safety functions)
100 ms (available time after sensor circuit is activated during manual start)
Start Pulse Length 500 ms minimum (manual reset)

rated conditions 17.3W (in IL² = 72 A²)
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation See chapter "Insulation Coordination"
Power
Name A1/A2
Rated control circuit supply voltage US 24V AC/DC ... 230V AC/DC -15 % / +10%
Rated control supply current IS Typical 103 mA (24V DC)
Typical 47 mA (48V DC)
Typical 38 mA (110V AC)
Typical 21 mA (230V AC)
US 2.7W (DC applicable)
2.9W (AC)
apparent power typical 5 VA (US)
Impulse current < 80 A (Us, & Delta;t = 50 & micro;s)
filter time 2 ms (at A1, at the voltage dip Us)
protection circuit 275V Varistor/411V Suppressor Diode

digital quantity: sensor circuit (S10,S12,S13,S22)
Input Description safety-related sensor inputs
IEC 61131-2 Type 3(S10, S12, S13)
Current, input (S10, S12, S13)
Current, output (S22)
Input Quantity 4
input voltage range, "0" signal 0V DC ... 5V DC (for safety shutdown; at S10/S12/S13)
input voltage range, "1" signal 11V DC ... 30V DC (S10/S12/S13)
Input current range "0" signal 0 mA ... 2 mA (for safety shutdown; at S10/S12/S13)
Impulse current < 5 mA (S10/S12/S13, usually US)
> -5 mA (S22 input, voltage is usually US)
filter time max. 1.5 ms (test pulse width of low test pulse)
test pulse rate = 5 x test pulse width
parallel
2702411

Phoenix PSR-MC32-3NO-1NC-24-230UC-SP-Safety Relays 2700525

Product Center