Phoenix EEM-EM357-measuring equipment 2908588,3-phase energy measuring equipment, suitable for measuring effective power by direct measurement in a power grid not exceeding 500V/80 A, with S0 output, with digital input and RS-485 interface, Has passed MID instruction certification

Product Type Energy Measuring Equipment
insulation characteristics
protection level II (EN 50470-1)
insulation characteristics
pollution level 2

dielectric strength 6 kV
4 kV (EN 50470-3,7.2)
power supply
Supply Voltage Range feed from measuring loop

measurement
Input Voltage Range 3x 184V ... 288V (320V ... 500 V)
Input current range 0.02 A ... 80 A
power consumption 3.5 VA (1 W)
Frequency Range 45Hz ... 65Hz
starting current Ist 0.02 A
Minimum current Imin 0.25 A
Limiting current Imax 80 A
Transient current Itr 0.5 A
Reference current Iref 5 A
Current transformer load 1.5 mΩ
effective energy (EN 50470-3) Class B
active energy (IEC 62053-21) Level 1
reactive power (IEC 62053-23) Level 2
digital quantity
Input Description active photoelectric isolation
Input Voltage Range 80V AC/DC ... 276V AC/DC

S0 output
Output Description passive photoelectric isolation
maximum switching voltage 27V DC
maximum switching current 27 mA
pulse time 50 ms ±2 ms
pause time 30 ms ±2 ms
Pulse LED 1000 imp/kWh
measurement constant 100 imp/kWh,kVAh,kvarh

measurement connection
Connection Mode screw connection
Rigid conductor cross section 1.5 mm² ... 35 mm²
Flexible Wire Cross Section 1.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG 16 ... 2 (rigid/flexible)
Tightening torque 2 Nm
Other Connections
Connection Mode screw connection
Rigid conductor cross section 0.14 mm² ... 1.5 mm²
Flexible Wire Cross Section 0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 26 ... 16 (rigid/flexible)
Tightening torque 0.5 Nm

Communications:
Communication Transport Protocol Modbus
communication standard RS-485
Transmission speed range 300 bps ... 57600 bps
Parity Even, Odd, None

width 72mm
height 90mm
depth 67mm

environmental conditions
protection level (front) IP51 (front)
protection level (interface) IP20 (interface)
ambient temperature (operation) -25°C ... 55°C
ambient temperature (storage/transport) -25°C ... 75°C
maximum allowable relative humidity (operating) 80%
1219095

Phoenix EEM-EM357-Measuring Equipment 2908588

Product Center