Phoenix EEM-EM377-measuring equipment 2908590,3-phase energy measuring equipment, suitable for measuring effective power through direct measurement in a power grid not exceeding 500V/80 A, with S0 output, Ethernet interface, has passed MID command certification

Product Type Energy Measuring Equipment
insulation characteristics
protection level II (EN 50470-1)
insulation characteristics
pollution level 2

dielectric strength 6 kV
4 kV (EN 50470-3,7.2)
power supply
Supply Voltage Range feed from measuring loop

measurement
Input Voltage Range 3x 184V ... 288V (320V ... 500 V)
Input current range 0.02 A ... 80 A
power consumption 3.5 VA (1 W)
Frequency Range 45Hz ... 65Hz
starting current Ist 0.02 A
Minimum current Imin 0.25 A
Limiting current Imax 80 A
Transient current Itr 0.5 A
Reference current Iref 5 A
Current transformer load 1.5 mΩ
effective energy (EN 50470-3) Class B
active energy (IEC 62053-21) Level 1
reactive power (IEC 62053-23) Level 2

S0 output
Output Description passive photoelectric isolation
maximum switching voltage 27V DC
maximum switching current 27 mA
pulse time 50 ms ±2 ms
pause time 30 ms ±2 ms
Pulse LED 1000 imp/kWh
measurement constant 100 imp/kWh,kVAh,kvarh

measurement connection
Connection Mode screw connection
Rigid conductor cross section 1.5 mm² ... 35 mm²
Flexible Wire Cross Section 1.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG 16 ... 2 (rigid/flexible)
Tightening torque 2 Nm
Other Connections
Connection Mode screw connection
Rigid conductor cross section 0.14 mm² ... 1.5 mm²
Flexible Wire Cross Section 0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 26 ... 16 (rigid/flexible)
Tightening torque 0.5 Nm

Communications:
Communication Transport Protocol Modbus/TCP
HTTP
NTP
DHCP
FTP
communication standard IEEE 802.3
Connection Mode RJ45
Transmission speed range 10 Mbps ... 100 Mbps

width 72mm
height 90mm
depth 67mm
1219095