Phoenix ELR H3-IES-PT/500AC-9-IOL-Hybrid Motor Starter 2908672, networkable hybrid motor starter for starting AC motors with more than 3 phases, height 500V AC,9 A output current, with adjustable overload break, emergency stop function to SIL 3/PL e and plug-in interface. Connect to IO-Link.

Product Type hybrid motor starter
Product Series CONTACTRON
Mode of operation 100% operating factor

phase number 3
Motor Starter Type direct starter
Switching frequency ≤ 2Hz (depending on load)
Switching frequency ≤ 2Hz (depending on load)
Maximum power loss 7W
minimum power loss 0.88W
type of coordination 1
power supply
Rated control circuit supply voltage US 24V DC
Control Supply Voltage Range 19.2V DC ... 30V DC
Rated control supply current IS 65 mA
protection circuit surge protection
polarity protection; parallel polarity protection diode
power supply: IO-Link
I/O power supply 24V DC (Power is supplied through the IO-Link interface of the IO-Link master station.)
power consumption Typical 65 mA ± 15% (24V DC)
Max. 150 mA
protection circuit polarity protection
short circuit protection
overload protection
insulation characteristics
Rated insulation voltage 550V
Rated overvoltage 6 kV
Overvoltage Level III
pollution level 2
control input and control supply voltage and insulation characteristics from auxiliary circuit to main circuit safety insulation (IEC 60947-1)
control input and control supply voltage to auxiliary circuits safety insulation (IEC 60947-1),≤ 300V AC in auxiliary circuits
safety insulation (EN 50178), in auxiliary circuits ≤ 300V AC
emergency trip
Operating Threshold > 60 A
response time < 0.5 s

control
Enter Name Enable Input
Rated operating voltage UC 24V DC
Trigger voltage range 19.2V DC ... 30V DC
Rated operating current IC 7 mA
Switch Threshold 9.6V ("0" signal)
19.2V ("1" signal)
switch level < 5V DC (for emergency stop)
Typical closing time < 30 ms
IO-Link
ports 1
Connection Mode COMBICON
connection system 3 lines
Specification V1.1.1
prevents polarity reversal is
cycle 30 ms
Process Data Volume 8 Byte (input data)
2 Byte (output data)

AC output
Considerations 1200V Semiconductor
Rated operating voltage Ue 500V AC
Operating voltage range 42V AC ... 550V AC
Rated operating current Ie 9 A (AC-51)
7 A (AC-53a)
mains frequency 50/60Hz
Load current range 1.5 A ... 9 A (see decay curve)
action characteristics according to IEC 60947-4-2 Class 10A
cooling time 20 min (for automatic reset)
leakage current 0 mA
protection circuit Surge protection; Varistor

control loop
Connection Mode in-line connection
stripping length 10mm
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 14
Load Circuit
Connection Mode in-line connection
stripping length 10mm
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 14
2900559

Phoenix ELR H3-IES-PT/500AC-9-IOL-Hybrid Motor Starter 2908672

Product Center