Phoenix PSR-SPP- 24DC/ESD/5X1/1X2/T10S-safety relay 2981509, safety relay, used for emergency stop and safety door monitoring, safety level up to SIL 3 or EN ISO 13849 standard Cat. 4, PL e, automatic or manual activation, 3 normally open contacts, 1 normally closed contact, 2 normally open contacts with 10 s fixed shutdown delay, pluggable direct plug-in terminal
| Product Type | safety relay |
| product series | PSRclassic |
| Application | Emergency stop button |
| safety door | |
| grating | |
| control | Single and Dual Channel |
| mechanical life | 10x 106Switch Times |
| Relay Model | Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3 |
| insulation characteristics | |
| Overvoltage Level | III |
| pollution level | 2 |
| rated conditions | 3.6W |
| Rated operating mode | 100% Eligible |
| Rated insulation voltage | 250V AC |
| rated overvoltage/insulation | 4 kV foundation safety isolation: Between all current paths and housing 6 kV reinforced isolation withstand voltage: Between 13/14, 23/24, 33/34 and the retention current path Between 13/14, 23/24, 33/34 |
| power supply | |
| Rated control circuit supply voltage US | 20.4V DC ... 26.4V DC |
| Rated control circuit supply voltage US | 24V DC -15 % / +10% |
| Overview | |
| US | Typical 3.6W |
| Rated control supply current IS | Typical 150 mA |
| Impulse current | 200 mA (US) |
| < 40 mA (Us/Ixto S10) | |
| < 150 mA (Us/Ixto S12) | |
| > -60 mA (Us/Ixto S22) | |
| < 40 mA (Us/Ixto S34) | |
| < 40 mA (Us/Ixto S35) | |
| power consumption | < 40 mA (Us/Ixto S10) |
| < 40 mA (Us/Ixto S12) | |
| > -40 mA (Us/Ixto S22) | |
| 0 mA (Us/Ixto S34) | |
| < 5 mA (Us/Ixto S35) | |
| input/start and feedback circuits | 24V DC -15 % / +10% |
| filter time | 1 ms (at A1, at the voltage dip Us) |
| max. 1.5 ms (at S10, S12; test pulse width) | |
| 7.5 ms (at S10, S12; test pulse rate) | |
| test pulse rate = 5 x test pulse width | |
| Typical Response Time | < 600 ms (auto start) |
| < 70 ms (manual reset) | |
| Typical startup time (Us) | < 600 ms (when controlled via A1) |
| Typical release time | < 20 ms (when controlled by s11/S12 and S21/S22) |
| < 20 ms (when controlled via A1) | |
| parallel | ∞ |
| Recovery Time | < 1 s |
| delay time | K3(t), K4(t) fixed by mode |
| Maximum switching frequency | 0.5Hz |
| protection circuit | Surge protection; Suppressor diode |
| Allowable total conductor resistance | about 11 Ω (US) |
| Operating voltage display | 1 x LED (green) |
| Status Display | 4 x LED (green) |
| Contact Type | 5 normally open safety contact outputs |
| 1 signal transmission current path | |
| Contact Material | AgSnO2 |
| maximum switching voltage | 250V AC/DC (note load curve) |
| Minimum Switching Voltage | 5V AC/DC |
| limit continuous current | 6 A (N/O contact, note attenuation) |
| 6 A (normally closed contact) | |
| Maximum impact current | 20 A (& Delta;t -100 ms, no delay contact) |
| 8 A (time delay contact) | |
| Minimum impulse current | 10 mA |
| the square of the total current value | 55 A2(pay attention to capacity reduction) |
| Maximum power rating (resistive load) | 144W (24VDC,t=0ms) |
| 288W (48VDC,t=0ms) | |
| 110W (110V DC, & tau; = 0 ms, delay contact: 77W) | |
| 88W (220VDC,t=0ms) | |
| 1500 VA (250V AC, & tau; = 0 ms, delay contact: 2000 VA) | |
| Maximum power rating (inductive load) | 42W (24V DC, & tau; = 40 ms, delay contact: 48W) |
| 42W (48V DC, & tau; = 40 ms, delay contact: 40W) | |
| 42W (110V DC, & tau; = 40 ms, delay contact: 35W) | |
| 42W (220V DC, & tau; = 40 ms, delay contact: 33W) | |
| Minimum on-off capacity | 50 mW |
| On-off capacity (360/h cycle) | 4 A (24V DC) |
| 4 A (230V AC) | |
| On-off capacity (3600/h cycle) | 2.5 A (24V (DC13)) |
| 3 A (230V (AC15)) | |
| output fuse | 10 A gL/gG (N/O contact) |
| 6 A gL/gG (normally closed contact) |