Phoenix PSR-SPP- 24DC/FSP2/2X1/1X2-coupling relay 2986588, safety coupling relay, can meet various SIL 2 application requirements, can connect digital output signal to I/O,2 normally open safety contact outputs, 1 signal contact, suitable for safe state closed applications, integrated test pulse filter, pluggable in-line connection terminal, width: 17.5mm

Product Type coupling relay
Product Series PSRclassic
Application Safety Shutdown
high requirements
low requirements
control single channel
mechanical life 10x 106Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical startup time (Us) 50 ms (when controlled by A1, with Us)
Typical release time 50 ms (when controlled by A1, with Us)
Recovery Time 1 s

rated conditions 2.4W
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation control circuits A1/A2), (31/32), (13/14), 23/24 6 kV
Power
Name A1/A2
Rated control circuit supply voltage US 24V DC -15 % / +10%
Rated control supply current IS typical value 55 mA (in UStypical)
US Typical 1.32W
Impulse current maximum 100 mA (in UStypical)
filter time max. 5 ms (Usvoltage dips)
max. 2 ms (test pulse width; high test pulse at A1/A2)
≥ 100 ms (test pulse width; high test pulse at A1/A2)
test pulse rate = 80 x test pulse width
max. 5 ms (test pulse width; low test pulse at A1/A2)
≥ 50 ms (test pulse rate; low test pulse at A1/A2)
test pulse rate = 15 x test pulse width
protection circuit Surge protection; Suppressor diode, 33V (A1-A2)

relay: enable current path (13/14, 23/24)
Output Description 2 x normally closed contacts, not delayed
outputs 2
Contact Type 2 normally open safety contact outputs
Contact Material AgCuNi,+ 0.2 µm Au
on-off capacity 75 mW minimum
Impulse current max. 5 A
limit continuous current 5 A
the square of the total current value 50 A2(pay attention to capacity reduction)
Switching frequency max. 0.5Hz
mechanical life 107Switch Times
output fuse 10 A gL/gG
relay: 31/32
Output Description 1 normally closed signal contact
outputs 1
Contact Type 1 feedback loop
Contact Material AgCuNi,+ 0.2 µm Au
on-off capacity 75 mW minimum
Impulse current Max. 100 mA
limit continuous current 100 mA
mechanical life 107Switch Times
output fuse 4 A gL/gG

connection technology
pluggable is
Wire Connection
Connection Mode in-line connection
Rigid conductor cross section 0.2 mm² ... 1.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 1.5 mm²
Flexible conductor cross-section, with sleeve, with plastic insulation sleeve 0.25 mm² ... 1.5 mm² (only with CRIMPFOX 6 wire clamps)
flexible conductor cross-section with cold press head without insulation sleeve 0.25 mm² ... 1.5 mm² (only with CRIMPFOX 6 wire clamps)
2900509

Phoenix PSR-SPP- 24DC/FSP2/2X1/1X2-coupling relay 2986588