Phoenix EMG 17-OV-12DC/60DC/3-solid state relay module 2954141, high-power solid state relay, with LED and protection circuit in the input and output circuits, input: 12V DC, output: 12 - 60V DC/max 3 A
| Product Type | Solid State Relay Module |
| Application | output function |
| Mode of operation | 100% operating factor |
| insulation characteristics | |
| insulation | Foundation Isolation |
| Data Management Status | |
| Last data maintenance date | 19.03.2025 |
| test voltage (input/output) | 3.5 kV AC (input/output) |
| Rated input voltage UN | 12V DC |
| relative to UNinput voltage range | 0.8 ... 1.2 |
| Input Voltage Range | 9.6V DC ... 14.4V DC |
| switch threshold "0" signal, reference UN | ≤ 0.4 |
| switch threshold "1" signal, reference UN | ≥ 0.8 |
| UN | 7 mA |
| Typical Response Time | 20 µs |
| Typical closing time | 200 µs |
| Status Display | LED (yellow) |
| protection circuit | polarity protection; polarity protection diode |
| Surge Protection | |
| sending frequency | 500Hz |
| Contact Type | 1 N/O contact |
| Digital Output Design | electronic |
| Rated output voltage | 60V DC |
| Output Voltage Range | 12V DC ... 60V DC |
| limit continuous current | 3 A (see Temperature Load Curve) |
| peak quiescent voltage | 60V DC |
| Voltage drop at maximum limited continuous current | 1.2V |
| output circuit | 2-wire connection, floating |
| protection circuit | polarity protection; polarity protection diode |
| Surge Protection |
| input side | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Connectable Guide Cross Section AWG | 24 ... 12 |
| output side | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Connectable Guide Cross Section AWG | 24 ... 12 |
| width | 17.5mm |
| height | 75mm |
| depth | 102mm |
| color | Green (RAL 6021) |
| flame retardant rating, according to UL 94 | V0 |
| environmental conditions | |
| protection level | IP20 |
| Ambient temperature (operation) | -20°C ... 60°C |