Phoenix FA MCR-EX-DS-I-I-OLP-digital display meter 2908800,Ex I, output loop power supply digital display meter installed in the control cabinet. HART

Product Type Digital Display
Product Series Field Analog
configuration Keyboard
Software

Function
configuration Keyboard
Software

maximum temperature coefficient < 0.02 %/K
Maximum transmission error 0.1 % (of terminal value)
Power
Supply Voltage Range loop power supply, no external power supply required

signals: current
current input signal 4 mA ... 20 mA
Maximum current input signal 200 mA
voltage drop ≤ 1V
≤ 3.9V (with display lamp)
input impedance 50 Ω.
signal: HART
current input signal up to 4x HART process variables
voltage drop ≤ 1.9V
≤ 4.8V (with display lamp)
input impedance Rx= 40 Ω/Cx= 2.3 nF

signals: current
current output signal 4 mA ... 20 mA
Display Bits 5
Display 7-segment LC display with backlight and dot matrix for text/column
display value can be extended
signal: HART
current output signal up to 4x HART process variables

Connection Mode in-line connection
stripping length 9mm
Rigid conductor cross section 0.14 mm² ... 1.5 mm²
Flexible Wire Cross Section 0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 26 ... 16

Explosion-proof installation (EPL) Gb
Div. 1
Intrinsically safe circuit (EPL) Gb
Div. 1

Data Communication (Bypass)
Supported Protocols HART

width 96mm
height 48mm
depth 41.5mm

color light gray (RAL 7035)
Shell Material Aluminum/Polycarbonate

environmental conditions
protection level IP65 (front)
IP20 (on the back)
ambient temperature (operation) -40°C ... 60°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation < 5000 m (above sea level)
climate class conforming to IEC 60654-1, Class B2
2908781

Phoenix FA MCR-EX-DS-I-I-OLP-Digital Display 2908800