Phoenix FA MCR-D-TUI-UI-2REL-UP-digital display 2907064, multi-function digital display, installed in the control panel electronic module housing, used to monitor and display analog measurement data. Common inputs can be connected to current, voltage, RTD and TC. 2 relay switching contact outputs and 1 analog output.

Product Type Digital Display
Product Series Field Analog
configuration Keyboard
Software
insulation characteristics
protection level I
insulation characteristics
Overvoltage Category II
pollution level 2

Function
configuration Keyboard
Software

Test Voltage 2500V
2500V
Test voltage output/power supply 2500V
Test voltage input/output 500V
test voltage, input/power supply 2.5 kV
2500V
Maximum transmission error ± 0.05 % (measurement range)
Electrical isolation input/output/power supply
electrical isolation 375V
power supply
Supply Voltage Range 24V AC/DC ... 230V AC/DC (-20 % ... +10 %,50Hz ... 60 Hz)
Maximum current consumption 30 mA
power consumption ≤ 6.9W

signals: current
Input Description Universal Input
Input Number 1
input signal current
current input signal 0 mA ... 20 mA +10%
4 mA ... 20 mA +10%
Maximum current input signal < 150 mA
valid input source current
input current 10 Ω
Transmitter supply voltage > 16V (22 mA)
Transmitter supply voltage range 22.8V ... 27.6V (no load)
Transmitter supply current < 30 mA (short circuit and overload protection)
D/A Converter Resolution 16 bits
signals: voltage
Input Description Universal Input
input signal voltage
voltage input signal 0V ... 10V
2V ... 10V
0V ... 5V
0V ... 1V
1V ... 5V
-1V ... 1V
-10V ... 10V
-30V ... 30V
-100 mV ... 100 mV
Maximum voltage input signal ± 35V (≥ 1 V)
± 12V (< 1 V)
valid input source voltage
input voltage > 1 MΩ
signal: resistance
Input Description Universal Input
input signal resistance
valid input source resistance: 30Ω... 3000Ω
measurement
Input Description Universal Input
configurable/programmable is
Available Sensor Types (RTDs) Platinum, Nickel, Copper Sensors
valid input source resistance thermometer
Temperature measurement range -200°C ... 1100°C (range depends on sensor type, adjustable)
connection system 2,3,4 lines
measurement rate 200 ms
measurement
Input Description Universal Input
configurable/programmable is
Available Sensor Types (TC) J, K, T, N, B, S, R, U. L, C, D
valid input source Thermocouple
Temperature measurement range -200°C ... 2495°C (range depends on sensor type, adjustable)
measurement rate 200 ms

switching: relay
Contact Type 2 changeover contacts
Minimum Switching Voltage 12V
maximum switching voltage 30V DC (3 A)
230V AC (3 A)
minimum switching current 10 mA
maximum switching current 3 A
switching: transistor
Output Description open collector output
outputs 1
Contact Type transistor
maximum switching voltage 28V
maximum switching current 200 mA
2907064