Phoenix VAL-MS 320/3 0 - 2 surge protector 2920230, used for surge protector of three-phase four-wire power supply system (L1,L2,L3,PEN), including base and protection plug, installed on NS 35 on the rail.
Product Type
surge protector
Product Series
VALVETRAB MS
IEC Category
II
T2
EN Type
T2
IEC power supply system
TN-C
type
DIN rail module, split, detachable
Bits
3
Surge protection fault alarm
with visual status indication window
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated frequency fN
50Hz (60 Hz)
Connection Mode
screw connection
thread
M5
Tightening torque
3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
stripping length
16mm
Flexible Wire Cross Section
1.5 mm² ... 25 mm²
Rigid conductor cross section
1.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG
15 ... 2
Connection Mode
fork cable end
Flexible Wire Cross Section
1.5 mm² ... 16 mm²
Dimensional drawing
width
53.4mm
height
89.8mm
depth
65.7mm (7.5mm with DIN rail)
Horizontal stitch pitch
3 Division
color
black (RAL 9005)
flame retardant rating to UL 94
V-0
material
600
insulation material
PA 6.6/PBT
Material Group
I
Shell Material
PA 6.6
PBT
protection channel
L-PEN
movement direction
3L-PEN
Rated voltage UN
240/415V AC (TN-C)
Rated frequency fN
50Hz (60 Hz)
Maximum continuous operating voltage UC
335V AC
Rated load current IL
80 A
Residual Flow IPE
≤ 1.35 mA
Standby power consumption PC
≤ 450 mVA
Nominal discharge current In(8/20)µs
20 kA
Maximum discharge current Imax(8/20) µs
40 kA
Rated short-circuit current ISCCR
25 kA
voltage protection level Up
≤ 1.5 kV
Residual pressure Ures
≤ 1.5 kV (In)
≤ 1.3 kV (10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
UT
415V AC (5 seconds/withstand mode)
440V AC (120 min/safe failure mode)
response time tA
≤ 25 ns
Maximum spare fuse with V-connection wire
80 A (gG)
maximum spare fuse with branch wiring
125 A (gG)
environmental conditions
protection level
IP20 (only if all connection bits are used)
ambient temperature (operation)
-40°C ... 80°C
ambient temperature (storage/transport)
-40°C ... 80°C
elevation
≤ 2000 m (amsl)
Allowable humidity (operating)
5%... 95%
Impact Force (Operation)
25g (half sine/11 ms/ 3x ± X,± Y, ± Z)
vibration (operation)
5g (10 ... 500Hz / 2.5 h / X,Y,Z)
2801164
넳넲
Phoenix VAL-MS 320/3 class 0 - 2 surge protector 2920230