Phoenix VAL-MS 500 ST-2 surge protector 2807609, type 2 surge protection connector, using high-power varistor, matching with VAL-OEZ base, temperature monitoring, optical fault alarm display. Working voltage: 500V AC

Product Type Spare Plug
Product Series VALVETRAB MS
IEC Category II
T2
EN Type T2
IEC power supply system TN
IT
type DIN rail module, split, detachable
distance between active and grounded components 5mm
Bits 1
Surge protection fault alarm with visual status indication window
can test protectors using the CHECKMASTER software tests:
insulation characteristics
Overvoltage Category III
pollution level 2

Rated frequency fN 50Hz (60 Hz)

Connection Mode pluggable

Dimensional drawing
width 17.5mm
height 52.4mm
depth 55.3mm
Horizontal stitch pitch 1 Partition

color black (RAL 9005)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6
Material Group I
Shell Material PA 6.6

protection channel L-PE
L-PEN
movement direction 1L-N/PE
Rated voltage UN 400/690V AC (TN)
500V AC (IT)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous operating voltage UC 600V AC
Residual Flow IPE ≤ 0.45 mA
Standby power consumption PC ≤ 250 mVA
Nominal discharge current In(8/20)µs 15 kA
Maximum discharge current Imax(8/20) µs 30 kA
Rated short-circuit current ISCCR 25 kA
voltage protection level Up ≤ 2.7 kV
Residual pressure Ures ≤ 2.7 kV (In)
≤ 2.5 kV (10 kA)
≤ 2.3 kV (at 5 kA)
≤ 2.2 kV (at 3 kA)
UT 690V AC (5 seconds/withstand mode)
762V AC (120 min/withstand mode)
response time tA ≤ 25 ns
maximum spare fuse with branch wiring 125 A (gG)

environmental conditions
protection level IP20
ambient temperature (operation) -40°C ... 80°C
ambient temperature (storage/transport) -40°C ... 80°C
elevation ≤ 2000 m (amsl)
Allowable humidity (operating) 5%... 95%
Impact Force (Operation) 25g (half sine/11 ms/ 3x ± X,± Y, ± Z)
vibration (operation) 5g (10 ... 500Hz / 2.5 h / X,Y,Z)

UL Specifications
Maximum continuous operating voltage MCOV(L-N) 600V AC
Rated discharge current In(L-N) 10 kA
protection channel L-N
Rated voltage 500V AC
Power Distribution System Single phase
Rated frequency 50/60Hz
Measured limit voltage MLV(L-N) 2370V
SPD Model 4CA

Standards/Specifications IEC 61643-11
Considerations 2011
Standards/Specifications EN 61643-11
Considerations 2012
2798844

Phoenix VAL-MS 500 ST-2 class surge protector 2807609

Product Center

PRODUCT CENTER