Phoenix S-PT-2XEX-48DC-surge protector 2800038, used for surge protection of two floating signal circuits in the screw-in module, the sensor head has IP67 protection level, can be directly installed on the field instrument, interface: M20 x 1.5. The tests were carried out according to the protection type of the following potentially explosive areas: Ex d/Ex tD/Ex ia IIC/Ex iaD. Suitable for fieldbus systems conforming to the FISCO concept. Can be used in safety-related circuits up to SIL 3.

Product Type measurement and control technology
product series SURGETRAB
IEC Category C1
C2
C3
D1
type protector can be screwed with the protected equipment
Bits 4
line pairs per module 2
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 48V DC

Connection Mode single line

Maximum internal capacitance CI 1.14 nF
Maximum internal inductance LI 1 µH
Maximum input current II 500 mA (T4 / ≤ 75°C)
500 mA (T5 / ≤ 75°C)
500 mA (T6 / ≤ 60°C)
Maximum input voltage UI 53V DC
Maximum input power PI 3.00W
grounding 500V AC
ambient temperature (operation) -40°C ... 75°C (T4)
-40°C ... 75°C (T5)
-40°C ... 60°C (T6)
Operating temperature range -40°C ... 100°C (T4)
-40°C ... 75°C (T5)
-40°C ... 60°C (T6)
maximum surface temperature 135°C (T4)
100°C (T5)
85°C (T6)

Dimensional drawing
width 28mm
height 28mm
depth 79mm

color steel/stainless steel color
sealing material NBR
Shell Material stainless steel 1.4404
ASTM 316L

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Earth Ground
Maximum continuous operating voltage UC 53V DC
37V AC
UC, the effective working current IC ≤ 5 µA
Residual Flow IPE ≤ 2 µA
Nominal discharge current In(8/20) & micro;s (core-core) 170 A
Rated discharge current In(8/20)& micro;s (core-ground) 10 kA
pulse discharge current Iimp(10/350) µs 1 kA
Total discharge current ITotal(8/20) µs 20 kA
Total discharge current ITotal(10/350) µs 2 kA
rated power pulse current lan (1000)& micro;s (core-core) 34 A
Output voltage limit 1 kV/& micro;s (core-to-core) peak ≤ 85V
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 1.1 kV
Output voltage limit 1 kV/& micro;s (core-core) static ≤ 80V
voltage protection level Up(core-core) ≤ 80V (C3 - 10 A)
voltage protection level Up(line-ground) ≤ 1.1 kV (C3 - 100 A)
≤ 1.1 kV (C1 - 1 kV / 500 A)
≤ 1.2 kV (C2 - 10 kV / 5 kA)
response time tA(core-core) ≤ 1 ns
response time tA (core-ground) ≤ 100 ns
input attenuation AE, symmetric. Typical 0.1 dB (1 MHz/50 Ω)
Typical 0.1 dB (500kHz/150 Ω)
cut-off frequency fg(3 dB),50 Ω symmetric system Typical 6 MHz
cut-off frequency fg(3 dB),150 Ω symmetric system Typical 3 MHz
capacitance (core-core) Typical 1 nF
capacitance (core-ground) 5 pF typical
Surge protection fault alarm None
Impact tolerance (line-line) C3 - 10 A
Impact resistance (line-ground) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 1 kA
alternating current carrying capacity (line-ground) 10 A - 1 s

environmental conditions
protection level IP67
ambient temperature (operation) -40°C ... 80°C (non-explosion-proof)
elevation ≤ 2000 m (amsl)
2800034

Phoenix S-PT-2XEX-48DC-Surge Protector 2800038

Product Center

PRODUCT CENTER