Phoenix ESSENTIAL-PS/1AC/24DC/240W/EE-power 2910587,ESSENTIAL edition power supply, primary switch mode, for DIN rail installation, input: 1 phase, output: 24V DC/240W
| AC operation |
| Rated input voltage range |
100V AC ... 240V AC |
| Input Voltage Range |
85V AC ... 264V AC |
| Attenuation |
< 100V (1 %/V) |
| AC input voltage range |
85V AC ... 264V AC |
| DC input voltage range |
120V DC ... 375V DC |
| Impulse current |
Typical 20 A (115V AC) |
| Typical 40 A (230V AC) |
| AC frequency range |
47Hz ... 63Hz |
| grid buffer time |
Typical 10 ms (115V AC) |
| Typical 20 ms (230V AC) |
| power consumption |
2.8 A (115V AC) |
| 1.4 A (230V AC) |
| Rated power consumption |
273.22 VA |
| protection circuit |
transient surge protection; varistor |
| Typical Response Time |
1000 ms |
| input fuse |
6.3 A (slow fuse, internal) |
| PE discharge current |
< 1 mA (264V AC) |
| efficiency |
88 % (115V AC) |
| 90 % (230V AC) |
| output characteristics |
HICCUP |
| Rated output voltage |
24V DC ±2% |
| output voltage (USet) setting range |
22V DC ... 28V DC (max. power ≤ 240W) |
| Rated output current (IN) |
10 A |
| Attenuation |
> 40°C (1.67 % / °C, 115V AC) |
| > 50°C (2.5 % / °C,230V AC) |
| Maximum capacitive load |
8000 μF |
| Active Current Limit |
105-150% of maximum output power (in case of short circuit) |
| control deviation |
≤ 1% (change of load, static 10%... 90%) |
| typical. ± 2% (change in load, dynamic 10%... 90%) |
| < 0.1 % (input voltage variation is ± 10 %) |
| residual wave |
< 120 mVSS(-10°C ... +70°C) |
| < 240 mVSS(-20°C ... -10°C) |
| output power |
240W |
| maximum no-load power consumption |
4.62W (115V AC) |
| 2.14W (230V AC) |
| Maximum rated load power loss |
31.53W (115V AC) |
| 25.44W (230V AC) |
| Input |
| Connection Mode |
screw connection |
| Minimum Wire Cross Section AWG |
16 |
| Maximum conductor cross section AWG |
12 |
| stripping length |
7mm |
| Output |
| Connection Mode |
screw connection |
| Minimum Wire Cross Section AWG |
16 |
| Maximum conductor cross section AWG |
12 |
| stripping length |
7mm |
| Signal Type |
LED |
| Operating voltage display |
Green LED |
| signal output |
| Status Display |
DC OK LED green |
| phase number |
1 |
| insulation voltage input/output |
3 kV AC |
| insulation voltage output/PE |
0.5 kV AC |
| insulation voltage input/PE |
2 kV AC |
| Product Type |
power supply |
| Product Series |
ESSENTIAL POWER |
| MTBF (Telcordia SR-332) |
> 700000 h |
| insulation characteristics |
| protection level |
I (with PE connection) |
| pollution level |
2 |