Phoenix FLT-SEC-T1-350/25-P-1/2 category surge protective connector 2905471, spare plug, used to FLASHTRAB SEC PLUS series lightning protection and surge protector, L-N and L-PEN path
Product Type
Spare Plug
Product Series
SEC Family
IEC Category
I / II
I
T1 / T2
T1
EN Type
T1 / T2
IEC power supply system
TN
TT
type
needle type
Bits
1
Surge protection fault alarm
with visual status indication window
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated frequency fN
50Hz (60 Hz)
Connection Mode
pluggable
Dimensional drawing
width
23.5mm
height
46.4mm
depth
59.4mm
Horizontal stitch pitch
Division 2
color
light gray (RAL 7035)
flame retardant rating, according to UL 94
V-0
material
600
insulation material
PA6.6-FR 20% GF
PBT-FR
Material Group
I
Shell Material
PA 6.6-FR 20 % GF
PBT-FR
protection channel
L-N
L-PEN
movement direction
L-N / L-PEN
Rated voltage UN
240V AC (TN)
240V AC (TT)
Rated frequency fN
50Hz (60 Hz)
Maximum continuous operating voltage UC
350V AC
Nominal discharge current In(8/20)µs
25 kA
impulse discharge current (10/350)& micro;s, charging
12.5
impulse discharge current (10/350)& micro;s, specific energy
160 kJ/Ω
impulse discharge current (10/350)& micro;s, peak limp
25 kA
Disconnect freewheeling capacity Ifi
25 kA (264V AC)
3 kA (350V AC)
Rated short-circuit current ISCCR
25 kA (264V AC)
3 kA (350V AC)
voltage protection level Up
≤ 1.5 kV
Residual pressure Ures
≤ 1.5 kV (In)
≤ 1.2 kV (10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
6 kV (1.2/50) & micro;s
≤ 1.5 kV
UT
415V AC (5 seconds/withstand mode)
457V AC (120 min/safe failure mode)
response time tA
≤ 25 ns
maximum spare fuse with branch wiring
315 A (gG)
Additional technical data
Maximum discharge current Imax(8/20) µs
100 kA
environmental conditions
protection level
IP20
ambient temperature (operation)
-40°C ... 80°C
ambient temperature (storage/transport)
-40°C ... 80°C
elevation
≤ 2000 m (amsl)
Allowable humidity (operating)
5%... 95%
Impact Force (Operation)
30g (half sine/11 ms/ 3x ± X,± Y, ± Z)
vibration (operation)
5g (5 - 500 Hz/2.5 h/X, Y, Z)
UL Specifications
Maximum continuous operating voltage MCOV
264V AC
Short Circuit Current Rating (SCCR)
50 kA
voltage protection standard VPR
1200V
Rated discharge current In
20 kA
protection channel
L-N
L-G
Rated voltage
240V AC
Power Distribution System
Single phase
Rated frequency
50/60Hz
SPD Model
1CA
2905346
넳넲