Phoenix FLT-SEC-T1-350/25-P-1/2 category surge protective connector 2905471, spare plug, used to FLASHTRAB SEC PLUS series lightning protection and surge protector, L-N and L-PEN path

Product Type Spare Plug
Product Series SEC Family
IEC Category I / II
I
T1 / T2
T1
EN Type T1 / T2
IEC power supply system TN
TT
type needle type
Bits 1
Surge protection fault alarm with visual status indication window
insulation characteristics
Overvoltage Category III
pollution level 2

Rated frequency fN 50Hz (60 Hz)

Connection Mode pluggable

Dimensional drawing
width 23.5mm
height 46.4mm
depth 59.4mm
Horizontal stitch pitch Division 2

color light gray (RAL 7035)
flame retardant rating, according to UL 94 V-0
material 600
insulation material PA6.6-FR 20% GF
PBT-FR
Material Group I
Shell Material PA 6.6-FR 20 % GF
PBT-FR

protection channel L-N
L-PEN
movement direction L-N / L-PEN
Rated voltage UN 240V AC (TN)
240V AC (TT)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous operating voltage UC 350V AC
Nominal discharge current In(8/20)µs 25 kA
impulse discharge current (10/350)& micro;s, charging 12.5
impulse discharge current (10/350)& micro;s, specific energy 160 kJ/Ω
impulse discharge current (10/350)& micro;s, peak limp 25 kA
Disconnect freewheeling capacity Ifi 25 kA (264V AC)
3 kA (350V AC)
Rated short-circuit current ISCCR 25 kA (264V AC)
3 kA (350V AC)
voltage protection level Up ≤ 1.5 kV
Residual pressure Ures ≤ 1.5 kV (In)
≤ 1.2 kV (10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
6 kV (1.2/50) & micro;s ≤ 1.5 kV
UT 415V AC (5 seconds/withstand mode)
457V AC (120 min/safe failure mode)
response time tA ≤ 25 ns
maximum spare fuse with branch wiring 315 A (gG)
Additional technical data
Maximum discharge current Imax(8/20) µs 100 kA

environmental conditions
protection level IP20
ambient temperature (operation) -40°C ... 80°C
ambient temperature (storage/transport) -40°C ... 80°C
elevation ≤ 2000 m (amsl)
Allowable humidity (operating) 5%... 95%
Impact Force (Operation) 30g (half sine/11 ms/ 3x ± X,± Y, ± Z)
vibration (operation) 5g (5 - 500 Hz/2.5 h/X, Y, Z)

UL Specifications
Maximum continuous operating voltage MCOV 264V AC
Short Circuit Current Rating (SCCR) 50 kA
voltage protection standard VPR 1200V
Rated discharge current In 20 kA
protection channel L-N
L-G
Rated voltage 240V AC
Power Distribution System Single phase
Rated frequency 50/60Hz
SPD Model 1CA
2905346

Phoenix FLT-SEC-T1-350/25-P-1/2 class surge protective connector 2905471