| movement direction |
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC |
53V DC |
| 37V AC |
| Rated current |
450 mA (45°C) |
| UC, the effective working current IC |
≤ 5 µA |
| Residual Flow IPE |
≤ 2 & micro;A (with PT 1X2-BE) |
| ≤ 1 & micro;A (with PT 1X2 F-BE) |
| Nominal discharge current In(8/20) & micro;s (core-core) |
10 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) |
10 kA |
| pulse discharge current Iimp(10/350) µs |
2.5 kA |
| Total discharge current ITotal(8/20) µs |
20 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-core) |
10 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) |
20 kA (total) |
| rated power pulse current lan (1000)& micro;s (core-core) |
18 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak |
≤ 70V |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 450V (with PT 1X2-BE) |
| ≤ 1 kV (with PT 1X2 F-BE) |
| Output voltage limit 1 kV/& micro;s (core-core) static |
≤ 70V |
| Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 25V (with PT 1X2-BE) |
| ≤ 50V (with PT 1X2 F-BE) |
| voltage protection level Up(core-core) |
≤ 80V (C1 - 1 kV / 500 A) |
| ≤ 85V (C2 - 2 kV/1 kA) |
| ≤ 120V (C2 - 10 kV / 5 kA) |
| voltage protection level Up(Line-Ground) |
≤ 450V (C1-1 kV / 500 A with PT 1X2-BE) |
| ≤ 550V (C2-2 kV / 1 kA with PT 1X2-BE) |
| ≤ 600V (C2-10 kV / 5 kA with PT 1X2-BE) |
| ≤ 800V (C1-1 kV / 500 A, F-BE with PT 1x 2) |
| ≤ 900V (C2-2 kV / 1 kA, F-BE with PT 1x 2) |
| ≤ 1000V (C2-10 kV / 5 kA with PT 1X2 F-BE) |
| response time tA(core-core) |
≤ 1 ns |
| response time tA (core-ground) |
≤ 100 ns |
| input attenuation AE, symmetric. |
Typical 0.5 dB (≤ 2 MHz / 50 Ω) |
| Typical 0.2 dB (≤ 600 kHz / 150 Ω) |