Phoenix SCK-C-MODBUS-PV string monitoring module 2901674, used to capture the SCK communication module of up to 8 SCK measurement modules, RS-485 Modbus/RTU output

Product Type Gateway/Proxy Server
product series SOLARCHECK
insulation characteristics
pollution level 2

rated conditions 0.65W
protection circuit surge protection; 33V suppressor diode
power supply
Rated supply voltage 24V DC -10 % ... +25%
Supply Voltage Range 21.6V DC ... 30V DC
Maximum current consumption 800 mA
current self-loss 22 mA (typical)
45 mA (max)
power consumption 580 mW (24V DC)

Connection Mode screw connection
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12
Tightening torque 0.5 Nm ... 0.6 Nm

data: Modbus/RTU
serial transmission rate 9.6/14.4/19.2/38.4 kbps
Connection Mode screw connection terminal
connection system 2,3 lines
Transmission Length ≤ 1200 m
terminal resistance 180 Ω (not in the scope of supply)
Supported Protocols Modbus/RTU
data: data interface for measuring or auxiliary modules
Supported Protocols patent

width 22.5mm
height 102mm
depth 106mm

environmental conditions
protection level IP20
ambient temperature (operation) -20°C ... 70°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation ≤ 2000 m
Allowable humidity (operating) ≤ 95% (non-condensing)
2901674

Phoenix SCK-C-MODBUS-PV string monitoring module 2901674