Phoenix CTM 2X1-24DC-Surge Protector-Plug and Plug 2838500,LSA-PLUS Protection Plug (COMTRAB CTM), Used for Protection of Single-side Grounded Two-wire Signal Circuit. Rated voltage: 24V DC
Product Type
measurement and control technology
Product Series
COMTRAB
IEC Category
B2
C1
C2
C3
D1
VDE requirement level
B2
C1
C2
C3
D1
type
LSA-PLUS module
Bits
2
Surge protection fault alarm
None
can test protectors using the CHECKMASTER software tests:
insulation characteristics
Overvoltage Category
II
pollution level
2
Rated voltage UN
24V DC
Connection Mode
can be inserted into COMTRAB-TERMIBLOCK and break/switch terminal strip LSA-PLUS
Dimensional drawing
width
9.5mm
height
21mm
depth
53.5mm
color
black (RAL 9005)
COPPER
flame retardant rating, according to UL 94
V-0
Shell Material
PA
Mechanical parameters
Open Side Panel
No
movement direction
Line-Line & Line-Earth Ground
Maximum continuous operating voltage UC
± 30V DC
21V AC
Rated current
380 mA AC (25 °C)
UC, the effective working current IC
≤ 5 µA
Residual Flow IPE
≤ 2 µA
Rated discharge current In(8/20)& micro;s (core-ground)
5 kA
pulse discharge current Iimp(350) & micro;s (core-ground)
1 kA
Total discharge current ITotal(8/20) µs
10 kA
Total discharge current ITotal(10/350) µs
2.5 kA
Maximum discharge current Imax(8/20) & micro;s (core-ground)
10 kA (total)
rated power pulse current lan (1000)& micro;s (core-ground)
100 A
Output voltage limit 1 kV/& micro;s (core-ground) peak
55V
Output voltage limit 1 kV/& micro;s (core-ground) static
≤ 45V
Residual voltage ln,(wire-ground)
≤ 50V
Ian(10/1000)& micro; Residual pressure at s (line-ground)
≤ 15V
voltage protection level Up(Line-Ground)
≤ 100V (C2-10 kV / 5 kA, peak)
≤ 45V (C2,10 kV/5 kA, static)
≤ 45V (C3-7.5 kV / 100 A, peak)
≤ 15V (C3-7.5 kV / 100 A, static)
2838513
넳넲
Phoenix CTM 2X1-24DC-Surge Protector-Plug and Plug 2838500