Phoenix PT 2X1-VF-120AC-surge protector 2859327, rail-mounted surge protector, used for high-voltage signal protection. The protection circuit has no leakage current and is used to protect 2 floating ground signals.
Rated voltage: 120V AC
| Product Type | measurement and control technology |
| product series | PLUGTRAB PT |
| IEC Category | C1 |
| C2 | |
| C3 | |
| type | DIN rail module, split, detachable |
| Bits | 2 |
| can test protectors using the CHECKMASTER software tests: | SW version 2.13 or later |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 120V AC |
| indicator/remote signaling | |
| switching function | normally closed contact |
| Connection Mode | screw connection (connection to the base) |
| thread | M3 |
| Tightening torque | 0.8 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 17.7mm |
| height | 90mm |
| depth | 51.7mm |
| Horizontal stitch pitch | 1 Partition |
| full module width | 17.7mm |
| Full module height | 90mm |
| full module depth | 65.5mm |
| color | black (RAL 9005) |
| flame retardant rating to UL 94 | V-0 |
| Shell Material | PA 6.6 |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Earth Ground |
| Maximum continuous operating voltage UC | 175V AC |
| Rated current | 6 A |
| UC, the effective working current IC | ≤ 2 µA |
| Residual Flow IPE | ≤ 4 µA |
| Nominal discharge current In(8/20) µs | 3 kA |
| pulse discharge current Iimp(10/350) µs | 300 A |
| Total discharge current ITotal(8/20) µs | 8 kA |
| Maximum discharge current Imax(8/20)µs | 8 kA |
| rated power pulse current lan (1000)& micro;s (core-ground) | 40 A |
| Output voltage limit 1 kV/& micro;s (core-ground) peak | ≤ 800V |
| Output voltage limit 1 kV/& micro;s (core-ground) static | ≤ 800V |
| residual voltage ln,(wire-ground) | ≤ 600V |
| protection level Up | ≤ 1 kV (C2 - 2 kA) |
| voltage protection level Up(line-ground) | ≤ 900V (C1 - 500 A) |
| ≤ 950V (C2 - 1 kA) | |
| ≤ 1 kV (C3 - 25 A) | |
| ≤ 1.1 kV (Iimp-300 A) | |
| response time tA | ≤ 100 ns |
| capacitance (core-ground) | Typical 3 pF |
| the resistance of each path | 0 Ω |
| Surge protection fault alarm | None |
| 6 A (gL/gG) |