Phoenix PACT RCP-4000A-UIRO-D95-current transformer 2906231, the kit includes a 4-terminal isolation amplifier (using screw connection technology) and a Rogowell coil (300mm long/95mm diameter) for AC current measurement of bus bars and power cables.
The isolation amplifier can output 8 different standard signals on the output side and has a switching output.
| Product Type | current transformer |
| insulation characteristics | |
| Overvoltage Category | II |
| pollution level | 2 |
| electrical isolation | reinforced insulation conforming to IEC 61010-1 |
| Typical measurement error | <1% |
| protection circuit | surge protection; 33V suppressor diode |
| step response (0-99%) | 110 ms |
| Rated insulation voltage | 300V |
| measuring coil | |
| wire structure signal line | 2x 0.22mm (signal wire (tinned)) |
| 1x 0.22mm (shielded wire (tinned)) | |
| insulation | double insulation |
| Rated insulation voltage | 1000V AC (rms CAT III) |
| 600V AC (rms CAT IV) | |
| Test Voltage | 10.45 kV DC (60 seconds) |
| Accuracy | 0.2 (IEC 61869-10: A1) |
| measuring transmitter | |
| Maximum transmission error | ≤ 0.5 % (from end of range) |
| Frequency Range | 16Hz ... 1000Hz |
| Test Voltage | 3 kV (50 Hz,1 min) |
| Overview | |
| can be calibrated | No |
| Converter Type | Rogowski coil and 4-way isolation amplifier |
| power supply: measuring transmitter | |
| Rated supply voltage | 24V DC |
| Rated supply voltage range | 9.6V DC ... 30V DC |
| power consumption | ≤ 1W (IOUT= 20 mA,9.6V DC,600 Ω load) |
| frequency | |
| Name | measuring coil |
| Frequency measurement range | 40Hz ... 20000Hz |
| signal | |
| signal input (at 50Hz) | 100 mV (1000 A) |
| Curve Type | Sine |
| input impedance | > 100 kΩ |
| current transformer | |
| configurable/programmable | via DIP switch |
| Rated frequency: Standard converter | 40Hz ... 20000Hz |
| Rated primary current Isn | 0 A AC ... 100 A AC |
| 0 A AC ... 250 A AC | |
| 0 A AC ... 400 A AC | |
| 0 A AC ... 630 A AC | |
| 0 A AC ... 1000 A AC | |
| 0 A AC ... 1500 A AC | |
| 0 A AC ... 2000 A AC | |
| 0 A AC ... 4000 A AC | |
| can be calibrated | No |
| Converter Type | Rogowski coil and 4-way isolation amplifier |
| switching: transistor | |
| outputs | 1 |
| Contact Type | 1 N/O contact |
| Minimum Switching Voltage | 1V |
| maximum switching voltage | 30V DC |
| minimum switching current | 100 µA |
| maximum switching current | 100 mA (at 30V) |
| signal | |
| Name | measuring coil |
| output signal (at 50Hz) | 100 mV (no load, 1000 A) |
| output voltage (no-load operation) | VOUT= M * dI/dt |
| output voltage (sinusoidal, no-load operation) | 100 mV (VOUT= 2 * & pi; * M * f * I(M = 0.318 μH; example: 50Hz;I = 1000 A)) |
| signal | |
| Name | measuring transmitter |
| configurable/programmable | is |
| voltage output signal | 0V ... 10V (via DIP switch) |
| 2V ... 10V (via DIP switch) | |
| 0V ... 5V (via DIP switch) | |
| 1V ... 5V (via DIP switch) | |
| 0V ... 10.5V (can be set via software) | |
| Maximum voltage output signal | 12.3V |
| current output signal | 0 mA ... 20 mA (via DIP switch) |
| 4 mA ... 20 mA (via DIP switch) | |
| 0 mA ... 10 mA (via DIP switch) | |
| 2 mA ... 10 mA (via DIP switch) | |
| 0 mA ... 21 mA (can be set via software) | |
| Maximum current output signal | 24.6 mA |
| load/output load voltage output | ≥ 10 kΩ |
| load/output load current output | ≤ 600 Ω (20 mA) |
| fluctuation | < 20 mVSS |
| < 20 mVSS | |