Phoenix PACT RCP-4000A-UIRO-PT-D95-current transformer 2906234, the kit includes a 4-terminal isolation amplifier (using plug-in connection technology) and a Rogowell coil (300mm long/95mm diameter) for AC current measurement of bus bars and power cables.
The isolation amplifier can output 8 different standard signals on the output side and has a switching output.

Product Type current transformer
insulation characteristics
Overvoltage Category II
pollution level 2

electrical isolation reinforced insulation conforming to IEC 61010-1
Typical measurement error <1%
protection circuit surge protection; 33V suppressor diode
step response (0-99%) 110 ms
Rated insulation voltage 300V
measuring coil
wire structure signal line 2x 0.22mm (signal wire (tinned))
1x 0.22mm (shielded wire (tinned))
insulation double insulation
Rated insulation voltage 1000V AC (rms CAT III)
600V AC (rms CAT IV)
Test Voltage 10.45 kV DC (60 seconds)
Accuracy 0.2 (IEC 61869-10: A1)
measuring transmitter
Maximum transmission error ≤ 0.5 % (from end of range)
Frequency Range 16Hz ... 1000Hz
Test Voltage 3 kV (50 Hz,1 min)
Overview
can be calibrated No
Converter Type Rogowell coil and 4-way isolation amplifier
power supply: measuring transmitter
Rated supply voltage 24V DC
Rated supply voltage range 9.6V DC ... 30V DC
power consumption ≤ 1W (IOUT= 20 mA,9.6V DC,600 Ω load)

frequency
Name measuring coil
Frequency measurement range 40Hz ... 20000Hz
signal
signal input (at 50Hz) 100 mV (1000 A)
Curve Type Sine
input impedance > 100 kΩ
current transformer
configurable/programmable via DIP switch
Rated frequency: Standard converter 40Hz ... 20000Hz
Rated primary current Isn 0 A AC ... 100 A AC
0 A AC ... 250 A AC
0 A AC ... 400 A AC
0 A AC ... 630 A AC
0 A AC ... 1000 A AC
0 A AC ... 1500 A AC
0 A AC ... 2000 A AC
0 A AC ... 4000 A AC
can be calibrated No
Converter Type Rogowell coil and 4-way isolation amplifier

switching: transistor
outputs 1
Contact Type 1 N/O contact
Minimum Switching Voltage 1V
maximum switching voltage 30V DC
minimum switching current 100 &micro;A
maximum switching current 100 mA (at 30V)
signal
Name measuring coil
output signal (at 50Hz) 100 mV (no load, 1000 A)
output voltage (no-load operation) VOUT= M * dI/dt
output voltage (sinusoidal, no-load operation) 100 mV (VOUT= 2 * & pi; * M * f * I(M = 0.318 μH; example: 50Hz;I = 1000 A))
signal
Name measuring transmitter
configurable/programmable is
voltage output signal 0V ... 10V (via DIP switch)
2V ... 10V (via DIP switch)
0V ... 5V (via DIP switch)
1V ... 5V (via DIP switch)
0V ... 10.5V (can be set via software)
Maximum voltage output signal 12.3V
current output signal 0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
0 mA ... 10 mA (via DIP switch)
2 mA ... 10 mA (via DIP switch)
0 mA ... 21 mA (can be set via software)
2906231

Phoenix PACT RCP-4000A-UIRO-PT-D95-Current Transformer 2906234