Phoenix VAL-SEC-T2-2S-175-FM-2 surge protector 2905351, plug-in surge protector, conforms to Class 2/Class II, used for 2-phase power network, zero-ground separation (4-wire system: L1, L2, N, PE), With remote communication contact.
Product Type
surge protector
Product Series
SEC Family
IEC Category
II
T2
EN Type
T2
IEC power supply system
TN-S
TT
type
DIN rail module, split, detachable
Bits
3
Surge protection fault alarm
visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated frequency fN
50Hz (60 Hz)
indicator/remote signaling
Connection Name
Remote alarm contact
switching function
changeover contact
Nominal operating voltage
5V AC ... 250V AC
125V DC (200 mA DC)
Operating current
5 mA AC ... 1 A AC
1 A DC (30V DC)
Connection Mode
screw connection
thread
M5
Tightening torque
4.5 Nm
stripping length
16mm
Flexible Wire Cross Section
2.5 mm² ... 16 mm²
Rigid conductor cross section
2.5 mm² ... 25 mm²
Attachable Guide Cross Section AWG
12 ... 4
Connection Mode
fork cable end
Flexible Wire Cross Section
1.5 mm² ... 6 mm²
Remote alarm contact
Connection Mode
COMBICON in-line/screw connection
thread
M2
Tightening torque
0.25 Nm
stripping length
7mm
Flexible Wire Cross Section
0.14 mm² ... 1.5 mm²
Rigid conductor cross section
0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG
28 ... 16
Dimensional drawing
width
37.3mm
height
97.9mm
depth
74.5mm (7.5mm with DIN rail)
Horizontal stitch pitch
Division 2
color (pin connector)
light gray (RAL 7035)
color (basic element)
gray (RAL 7042)
flame retardant rating, according to UL 94
V-0
material
600
insulation material
PA6.6-FR 20% GF
PBT-FR
Material Group
I
Shell Material
PA 6.6-FR 20 % GF
PBT-FR
protection channel
L-N
L-PE
N-PE
movement direction
2L-N & N-PE
Rated voltage UN
120/208V AC (TN-S)
120/208V AC (TT)
2905339
넳넲
Phoenix VAL-SEC-T2-2S-175-FM-2 class surge protector 2905351