Phoenix QUINT4-PS/1AC/110DC/4-power supply 2904613, primary switching power supply QUINT POWER, screw connection, DIN rail installation, input: 1 phase, output: 110V DC/4 A
| Control Input (Configurable) Rem |
output power ON/OFF (SLEEP MODE) |
| Default (Value) |
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SGND) |
| AC operation |
| Rated input voltage range |
100V AC ... 240V AC |
| Input Voltage Range |
100V AC ... 240V AC -10 % ... +10% |
| Attenuation |
< 100V AC (1 %/V) |
| maximum dielectric strength |
300V AC 60 s |
| National Grid Typical Voltage |
120V AC |
| 230V AC |
| Supply Voltage |
AC |
| Impulse current |
Typical 11 A (at 25°C) |
| impulse current integral (I2t) |
< 0.3 A2s |
| Surge current limit |
11 A |
| AC frequency range |
50Hz ... 60Hz-10%... + 10% |
| frequency range (fN) |
50Hz ... 60Hz-10%... + 10% |
| grid buffer time |
Typical 37 ms (120V AC) |
| Typical 38 ms (230V AC) |
| power consumption |
6.3 A (100V AC) |
| 5 A (120V AC) |
| 2.6 A (230V AC) |
| 2.5 A (240V AC) |
| Rated power consumption |
474 VA |
| protection circuit |
transient surge protection; varistor, gas discharge tube |
| power factor (cos phi) |
0.94 |
| Suction time |
< 1 s |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| input fuse |
12 A (slow fuse, internal) |
| recommend use |
10 A ... 16 A (characteristics B, C or similar) |
| PE discharge current |
< 3.5 mA |
| 0.7 mA (264V AC,60 Hz) |
| DC operation |
| Rated input voltage range |
110V DC ... 250V DC |
| Input Voltage Range |
110V DC ... 250V DC -18 % ... +40% |
| Attenuation |
< 110V DC (1 %/V) |
| Supply Voltage |
DC |
| power consumption |
5.6 A (110V DC) |
| 2.3 A (250V DC) |
| efficiency |
Typical 93.5 % (120V AC) |
| Typical 94.7 % (230V AC) |
| output characteristics |
U/ I Advanced |
| Smart HICCUP |
| FUSE MODE |
| Rated output voltage |
110V DC |
| output voltage (USet) setting range |
110V DC ... 135V DC (constant capacity) |
| Rated output current (IN) |
4 A |
| Static Boost (IStat.Boost) |
5 A |
| Dynamic Boost (IDyn.Boost) |
6 A (5 s) |
| selective fusing (ISFB) |
24 A (15 ms) |
| Type of thermal magnetic circuit breaker |
A1. .. A4 / B2 ... B4 / C1 ... C2 / Z1 ... Z4 |
| Attenuation |
> 60°C ... 70°C (2.5 %/K) |
| feedback voltage resistance |
≤ 160V DC |
| output |
< 150V DC |
| control deviation |
< 0.5 % (static load change 10% ... 90%) |
| <4% (dynamic load change 10% ... 90%,(10Hz)) |