| movement direction |
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC |
13V DC |
| 9V AC |
| Rated current |
450 mA (45°C) |
| UC, the effective working current IC |
≤ 5 µA |
| Residual Flow IPE |
≤ 1 & micro;A (with PT 1X2 + F-BE) |
| ≤ 2 & micro;A (with PT 1X2-BE) |
| Nominal discharge current In(8/20) & micro;s (core-core) |
10 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) |
10 kA |
| pulse discharge current Iimp(10/350) µs |
2.5 kA |
| Total discharge current ITotal(8/20) µs |
20 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-core) |
10 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) |
10 kA |
| rated power pulse current lan (1000)& micro;s (core-core) |
67 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak |
≤ 20V |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 450V (with PT 1X2-BE) |
| ≤ 1 kV (with PT 1X2 + F-BE) |
| Output voltage limit 1 kV/& micro;s (core-core) static |
≤ 18V |
| Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 25V (with PT 1X2-BE) |
| ≤ 50V (with PT 1X2 + F-BE) |
| Residual voltage ln,(wire-wire) |
≤ 18V |
| Residual voltage lan(10/1000)& micro;s (wire-wire) |
≤ 23V |
| voltage protection level Up(core-core) |
≤ 50V (C2 - 10 kV / 5 kA) |
| voltage protection level Up(Line-Ground) |
≤ 450V (C1-1 kV / 500 A with PT 1X2-BE) |
| ≤ 1000V (C2-10 kV / 5 kA, with PT 1X2 + F-BE) |
| voltage protection level Upstatic (core-core) |
≤ 18V (C2 - 10 kV / 5 kA) |
| voltage protection level Upstatic (core-ground) |
≤ 50V (C2-10 kV / 5 kA with PT 1X2-BE) |
| ≤ 100V (C2-10 kV / 5 kA with PT 1X2 + F-BE) |
| response time tA(core-core) |
≤ 1 ns |
| response time tA (core-ground) |
≤ 100 ns |
| input attenuation AE, symmetric. |
Typical 0.5 dB (≤ 600 kHz / 50 Ω) |
| Typical 0.2 dB (≤ 200 kHz / 150 Ω) |
| Typical 0.1 dB (≤ 50 kHz/600 Ω) |
| cut-off frequency fg(3 dB),50 Ω symmetric system |
Typical 3 MHz |
| cut-off frequency fg(3 dB),150 Ω symmetric system |
Typical 1 MHz |
| cut-off frequency fg(3 dB),600 Ω symmetric system |
Typical 300 kHz |
| capacitance (core-core) |
Typical 3 nF |
| capacitance (core-ground) |
Typical 4 pF (with PT 1X2-BE) |
| Typical 2 pF (with PT 1X2 + F-BE) |
| the resistance of each path |
2.2 Ω ± 10% |
| Surge protection fault alarm |
None |
|
500 mA (T) |
| Impact tolerance (line-line) |
C2 - 10 kV / 5 kA |
| C3 - 67 A |
| Impact resistance (line-ground) |
C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA |
| D1 - 2.5 kA |